EnDat 
In the Bits text field specify the number of bits used for single turn resolution (see encoder 
data sheet). In the Number of Revolutions text field specify the number of turns (see 
encoder data sheet). Optionally, check Enable Incremental 1Vpp sin/cos. 
If your encoder has an analog output, select Enable Incremental. 
Select line count, interpolation number and interpolated counts. 
!
WARNING 
When a battery error exists, absolute position may not be true (whether 
the Ignore Battery Error option has been checked or not). 
FAILURE TO HEED THIS WARNING CAN CAUSE EQUIPMENT 
DAMAGE, INJURY, OR DEATH. 
Resolver 
Optionally modify the feedback resolution by changing the value in Counts Per Rev. 
Default: 16384. 
Halls 
With amplifier set to Use Halls for Velocity/Position, optionally increase the counts per 
rev ratio by incrementing the Halls Count Multiplier.  
If two feedback devices are installed, verify that the values of Motor Turns to Position 
Turns correctly represent the ratio of motor encoder turns to position encoder turns. The 
details of the following screen may vary depending on the types of feedback devices 
present. 