CME 2 User Guide    Digital Inputs and Outputs 
Copley Controls  65 
6.2.5: Custom Output Settings: Position Triggered Output 
Any of the amplifier’s digital outputs can be programmed to respond in certain ways to the 
position of the controlled axis. The output goes active when the axis position meets the 
specified criteria. 
Configure a Position Triggered output 
1 
Choose Custom Position Triggered Output for an output and then click Configure 
Custom to open the In Position Configuration screen. 
2 
Select one of the configurations described below and enter appropriate values for the 
parameters. 
Configuration 
Description and Parameters 
1.   
In Position 
Window 
Activates the output while the axis is in the window between the programmed Upper 
and Lower positions.  
2.   
Trigger at 
Position 
Activates the output for the programmed Time when the axis travels through the 
programmed Position. 
3.   
Trigger Positive 
Motion 
Activates the output for the programmed Time when the axis travels in the positive 
direction through the programmed Position. 
4.   
Trigger Negative 
Motion 
Activates the output for the programmed Time when the axis travels in the negative 
direction through the programmed Position. 
3 
Choose Output Active High to have the output go high when active or Output Active Low 
to have the output go low when active. 
4 
In stepper mode with no encoder, choose Use Limited Position. Otherwise choose Use 
Actual Position. 
5 
Click OK to save changes to amplifier RAM and close the 
Custom Output Configuration screen. 