User guide
Command Inputs    CME 2 User Guide 
70  Copley Controls 
7.1: Analog Command Settings 
View or change the settings described below. 
Parameter 
Description 
Scaling 
Current mode: output current produced by +10 Vdc of input.  
Range: 0 to 10,000,000 A. Default: Peak Current value. 
Velocity mode: output velocity produced by +10 Vdc of input.  
Range: 0 to 100,000 rpm (mm/sec). 
Default: Maximum Velocity value. 
Position mode: position change (counts or mm) produced by +10 Vdc of input. 
Range: 0 to 1,000,000,000 counts. 
Default: 1 Revolution of a rotary motor or 1 pole pair distance for a linear motor. 
For more information, see Scaling (p. 71). 
Dead Band 
Sets dead band. Range: -10,000 to 10,000 mV. Default: 0. 
For more information, see Dead Band (p. 71). 
Invert Command 
Inverts polarity of amplifier output with respect to input signal. 
Offset 
(Current and Velocity modes only.) Used to offset input voltage error in an open 
loop system. Not recommended for use when the amplifier is part of a closed loop 
system. 
Range: -10,000 to 10,000 mV. Default: 0. For more information, see  
Offset (p. 72). 
For more information, see Analog Command Notes (p 71). 










