8.1: CAN Network 
A CANopen network can support up to 127 nodes. Each node must have a unique and 
valid seven-bit address (Node ID) in the range of 1-127. (Address 0 should only be used 
when the amplifier is serving as a CME 2 serial port multi-drop gateway.) 
Configure a CAN interface 
1 
Verify that the CAN network has been cabled and terminated as per amplifier documents. 
2 
 Click CAN Configuration to open the CAN Configuration screen. (If CAN is 
not the Position Loop Input, choose AmplifierNetwork Configuration instead.) 
3 
Choose network type (CAN or DeviceNet). This is optional for some drives. 
4 
Choose a Bit Rate and choose any combination of address sources (Switch, Inputs, and 
Programmed Value). The address is the sum of the values from these sources. 
5 
For each source selected, perform the additional steps described below. 
Source 
Additional Steps 
Use Switch 
Verify the S1 switch setting. (Assigns values for Bit 0 – Bit 3 of CAN address.) 
Use Inputs 
Enter Number of Inputs. Choose an input to represent each CAN address bit. 
Use Programmed Value 
Enter the Programmed Value.  
6 
Click Save & Reset to save changes to amplifier flash, close the screen, and reset the 
amplifier. Click Save & Close to save changes to amplifier flash without resetting. 
NOTE: Address and bit rate changes take effect only after power-up or reset. 