Continuous Flow Icemaker Service Manual
Continuous Flow Icemaker Service Manual
Publication Number: 630460174SER - 18 - © 2004-2005, IMI Cornelius Inc.
OVERLOAD CHECK
COMPRESSOR CHECK
CAPACITOR CHECK
Using a volt–ohmmeter check the continuity 
across the overload, contact #1 and #3. If none, 
wait for unit to cool down and try again. If still no 
continuity, the overload protector is defective 
and should be replaced.
FIGURE 18. OVERLOAD CHECK
The resistance readings on the windings will be 
between 0.25 to 10.00 ohms, a meter capable of 
these low readings must be used.
1. Check between “C” and “R.” Replace the 
compressor if there is no continuity as the 
run windings are open.
2. Check between “C” and “S.” Replace the 
compressor if there is no continuity as the 
start windings are open.
FIGURE 19. COMPRESSOR CHECK
3. Check between “C” and “R” or “S” and the shell of the compressor. If there is continuity, replace the 
compressor as the motor is grounded.
4. Check between screw terminal on the overload and “C” on the compressor. Check and repair the 
lead or connections if there is no continuity.
1. Check or replace start capacitor, 
disconnect bleed resistor before checking 
for shorted capacitor.
2. Check or replace run capacitor (if 
supplied) check for shorted capacitor or 
either terminal grounded to case.
FIGURE 20. GEAR MOTOR OVERLOAD
GEAR MOTOR OVERLAY