GENERAL INFORMATION
INTRODUCTION
Cornelius CH Series, Refrigerated Recirculating Water Chillers are designed to provide a continuous flow of clean
cooling water at a constant temperature and to handle a variety of closed loop and tank cooling applications.
The CH Series consists of a refrigeration system with associated operating controls housed in a sturdy sheet metal
cabinet. A standard pump and reservoir package provides a complete self-contained water cooling and circulating
system.
CH Series Chillers are designed to operate in a clean laboratory or industrial environment where ambient temperatures
range from 50°F to 100°F. Once properly installed, CH Series Chillers run virtually maintenance free and provide a
constant supply of cooling liquid to the application.
Specifications
The CH Series specifications are shown in Table 1.
Specification Notes
1. The figures for power and cooling capacity are listed for air-cooled units with a circulation temperature
of 68° F and ambient temperature of 80°F and standard pump.
2. Cooling capacity will be affected as follows: Derate 17% for 50 Hz operation. Derate 1% for each ° F
drop in recirculating temperature. Derate 0.5% for each ° F increase in ambient temperature.
3. The operating water temperature range for water is 50° F (10° C) to 100° F (38° C). If uses of other
fluids or temperatures are required, the Technical Service Department must be contacted so the
appropriate ranges can be set.
4. All CH Series Chillers are thoroughly tested before leaving the factory to ensure that each unit meets
these specifications prior to shipment.
LOCATION
Install the Chiller indoors in a well ventilated area where ambient temperatures will never fall below 50° F or rise above
110° F. To obtain optimum cooling capacity, the ambient temperature should be 80° F or below.
Standard CH Chillers have air-cooled condensers. On air-cooled units it is important that the air intake and discharge
are not obstructed. Avoid hot air discharge from other equipment or enclosed areas where heat build-up could cause a
significant rise in ambient temperatures. A minimum of two feet of space on all four sides of the Chiller will be sufficient
to prevent obstruction.
Table 1.
Model CH3000
Cooling capacity, Watts/BTU/hr 10550/36000
Compressor 3 HP
Condenser Air Cooled
Temperature Controller
Digital Display 40
o
-100
o
F
Pump Many Available
Reservoir (Capacity) 10 Gallons
Voltage (Full Load Amps) 460/60/3 (9)
Dimensions W x D x H (inches) 28 x 28 x 41
Inlet/Outlet Fitting Size 3/4-inch