Corning Optical Communications DRAFT User Manual I CMA-XXX-AEN I Page 30
3.1.2 Power and Heat Specifications Summary
Table 3-3 provides the power, heat and rack specifications for the equipment installed in the headend/telco rooms.
Unit
Description
Min-Max Voltage (VAC)
Max Power Draw
(Watts)
No. of
Units
Heat (BTU/hr)
IHU Integrated headend unit 100 220 300 1 1020
PSU6 Six Unit DC power supply unit
85 to 265
1200
(100 W per port)
1 512
(typical at 100 V in)
Table 3-3. Power and Heat Specifications
3.1.3 Dimensions, Weight and Rack Specifications of Units
Table 3-4 describes the physical specifications of the Corning
optical network evolution (ONE
) solution units described in this
manual.
Unit
Dimensions (H x W x D)
Rack Space
19-in (RU)
Weight: lbs [kg]
IHU 7 x 17.3 x 15.5 in
[177.8 x 440 x 394 mm]
4 Chassis: 30 lbs (14 kg)
Per RIM: 1.9 lbs (0.9 kg)
Per RIX: 1.54 lbs (0.7 kg)
Per OIM: 1.5 lb (0.7 kg)
Per OIX: 1.54 lb (0.7 kg)
ACM: 2.2 lb (1.0 kg)
PSM: 1.98 lb (0.9 kg)
PSU6 1.73 x 17.51 x 13.74 in
[44 x 445 x 349 mm]
1
Enclosure: 6.22 lb (2.825 kg)
Per PSM-I module: 0.8 lb (0.36 kg)
MRU
10.5 x 17.5* x 15.75 in (266.7 x 445 x 400 mm)
*without rack brackets
6
Chassis without PAMs: 48 lbs (21.8 kg)
Each PAM: 4.7 lbs (2.15 kg)
Table 3-4. Dimensions, Weight and Rack Specifications of Headend/Intermediate Units
3.2 Infrastructure Preparation
The following installation rules are based on the assumption that the site survey and installation planning (including power
requirements) have been completed.
3.2.1 Site Considerations
The distance between the MRU service antenna and the coverage area should correspond to line of sight (LoS)
requirements for maximum coverage area.
The maximum fiber path loss is 5 dB.
The system delay of the optical system must be taken into consideration when there are neighboring BTS sites overlapping
in coverage.