Corning Optical Communications User Manual I CMA-490-AEN I Page 79
Figure 6-21. Location of External Alarms Connector and Cabinet Alarms Block
3. Connect the external alarm connections to the cabinet.
Table 6-6 provides the dry contact alarms cable wiring description.
Color Description
Red +48 V_COMMON
Green N48 V_EXIST INDICATION
Brown N48 V_DOOR ALARM
Black N48 V_HEX ALARM
White N48 V_FUTURE ALARM
Table 6-6. Dry Contact Alarm Cable Wiring Info
Refer to Table 6-7 for wiring description of MRU External Alarms connector and to Figure 6-22 for examples of the upper
and lower cabinet block wiring connections.
External Alarms Connector Pin No.
1 Common
6 Door Alarm
2 NC
7 HEX Alarm
3 NC
8 Future Alarm
4 NC
9 Exist Indication