Specifications
6 Others
6.1 Output Current Monitor
¿
PBA300F, PBA600F, PBA1000F, PBA1500F
and PBA1500T
¡
You can monitor an output current by measuring a voltage be-
tween the terminal CB and the terminal -S on either CN1 or CN2.
¡
Fig.6.1 shows the relationship between the voltage of the terminal
CB and the output current.
Fig.6.1 shows a typical characteristic of PBA1500F-5. Please
contact us for the characteristics of the other models.
The output current shown in Fig.6.1 should be used only as a
guide.
¿
PBA300F, PAB600F, PBA1000F, PBA1500F
and PBA1500T
*
Values with
*
are based on the assumption that fan maintenance
will be properly done.
¿
PBA300F, PAB600F, PBA1000F, PBA1500F
and PBA1500T
¡
Fans should be exchanged on a regular basis because their life
expectancy (R (t) = 90%) vary depending on use conditions as
shown in Fig.5.5. Please see ”Optional Parts” for details about
fan units.
¡
Warranty
¿
PBA10F, PBA15F, PBW15F, PBA30F,
PBW30F, PBA50F, PBW50F, PBA75F,
PBA100F and PBA150F
¿
PBA300F, PAB600F, PBA1000F, PBA1500F
and PBA1500T
¡
The warranty period is 5 years if a power supply is used within a
derating curve.
5.3 Expected Life and Warranty
¡
Expected Life
Please see the following tables for expected life.
¿
PBA10F, PBA15F, PBW15F, PBA30F,
PBW30F, PBA50F, PBW50F, PBA75F,
PBA100F and PBA150F
AC-DC Power Supplies Enclosed type
Instruction Manual
PBA/PBW-42
PBA/PBW
Fig.6.1 Load current conversion graph(PBA1500F-5)
Voltage of
CB terminal
0
-2
2
-4
-6
[V]
100 200 300
Load current
[A]
Fig.5.5 Life expectancy of fan
Ambient temperature[
C
]
[H]
Life expectancy of fan
4030 50 60 70 80
10,000
100,000
500,000
Annual Average of Ambient
Temperatures
Load Factor
50% 100%
All Mounting
Methods
Ta = 40
C
or less 7 years
*
7 years
*
Ta = 50
C
6 years
*
5 years
Mounting
Method
Annual Average of
Ambient Temperatures
Load Factor
50% 100%
A
Ta = 40
C
or less 5 years 5 years
Ta = 50
C
5 years 3 years
B and C
Ta = 30
C
or less 5 years 5 years
Ta = 40
C
5 years 3 years
Mounting
Method
Annual Average of
Ambient Temperatures
Load Factor
50% 100%
A
Ta = 30
C
or less 10 years or more 10 years or more
Ta = 40
C
10 years or more 6 years
Ta = 50
C
5 years 3 years
B and C
Ta = 20
C
or less 10 years or more 10 years or more
Ta = 30
C
10 years or more 6 years
Ta = 40
C
5 years 3 years