Full Product Manual
WARNING
18
3-WIRE CONNECTION (GROUNDED NEUTRAL) - U.S.A. ONLY.
Electrical Shock Hazard
Grounding through the neutral conductor is prohibited for new
branch-circuit installations (1996 NEC); mobile homes; and
recreational vehicles, or in an area where local codes prohibit
grounding through the neutral conductor. For installations where
grounding through the neutral conductor is prohibited, see the
Ungrounded Neutral graphic.
Use grounding terminal or lead to ground unit.
Connect neutral terminal or lead to branch circuit neutral in
usual manner.
Failure to do so could result in death, fire or electric shock.
3-Wire Cable from Home Power Supply
IMPORTANT: Use the 3-wire cable from home power supply where local codes
permit a 3-wire connection.
1
. Disconnect power.
G
rounded Neutral
e
i
g
h
f
a
b
c
d
a Junction Box
b Black Wires
c Neutral (White)
Wires
d Ground (Green or
Bare) Wire
e Cable from Range
f UL Listed Conduit
Connector
g Red Wires
h UL Listed Wire Connectors
i House Electrical Supply
Installation Instructions
19
2.
Connect the 2 black wires
b together using a UL listed wire connector.
3
.
Connect the 2 neutral (white) wires
c and the ground (green or bare) wire d
(of the range cable) using a UL listed wire connector.
4
.
Connect the 2 red wires
g together using a UL listed wire connector.
5
. Install junction box cover.
4-WIRE CONNECTION (UNGROUNDED NEUTRAL)- U.S.A. ONLY
4-Wire Cable from Home Power Supply
IMPORTANT: Use the 4-wire cable from home power supply in the U.S. where
local codes do not allow grounding through neutral, New Branch circuit
installations (1996 NEC), mobile homes and recreational vehicles, new
construction and in Canada.
1
. Disconnect power.
U
ngrounded Neutral
i
b
c
d
g
f
e
h
a
a Junction Box
b Black Wires
c Red Wires
d Cable from Range
e UL listed or CSA
Approved Conduit
Connector
f Ground (Green or
Bare) Wires
g UL Listed Wire
Connector
h Neutral (White) Wires
i House Electrical Supply
2
.
Connect the 2 black wires b together using a UL listed wire connector.
3
.
Connect the 2 red wires
c together using a UL listed wire connector.
4
. Untwist white wire from green (or bare) ground wire coming from the range.
5
.
Connect the 2 neutral (white) wires
h together using a UL listed
wire connector.
6
.
Connect the ground (green or bare) wire
f from the oven cable to the
ground (green or bare) wire (in the junction box) using a UL listed wire
connector.
7
. Install junction box cover.
Installation Instructions