Installation Guide

15 16
RIGID PIPE CONNECTION:
The rigid pipe connection requires a combination of pipe fittings to obtain an in-line connection
to the range. The rigid pipe must be level with the range connection. All strains must be
removed from the supply and fuel lines so range will be level and in line. (See Figure 4)
MUST INCLUDE A SHUTOFF VALVE:
The supply line must be equipped with a manual shutoff valve. This valve should be located in
the same room but external to the range in an easily accessible location. It should be in a
location that allows ease of opening and closing. Do not block access to shutoff valve. The
valve is for turning on or shutting off gas to the range. (See Figure 5)
Be sure you know where and how to shut off the gas supply to the range.
GAS PRESSURE REGULATOR:
The pressure regulator must be connected in series with the manifold of the appliance and
must remain in series with the supply line regardless the type of gas being used.
For proper operation, the gas pressure regulator supplied with this range must be used. The
inlet pressure to the regulator should be as follows:
Figure 4
Figure 5
NATURAL GAS
BURNER POSITION NOZZLE
DIAMETER
MINIMUM
PRESSURE
MAXIMUM
PRESSURE
Auxiliary Front Right 1 x 1.10 4” 14”
Semi-Rapid Rear Left & Right 2 x 1.29 4” 14”
Rapid Front Left 1 x 1.45 4” 14”
Triple Ring Center 5 x 0.99 4” 14”
LIQUID PETROLEUM (LP) GAS
BURNER POSITION NOZZLE
DIAMETER
MINIMUM
PRESSURE
MAXIMUM
PRESSURE
Auxiliary Front Right 1 x 0.70 10” 14”
Semi-Rapid Rear Left & Right 2 x 0.80 10” 14”
Rapid Front Left 1 x 0.89 10” 14”
Triple Ring Center 5 x 0.56 10” 14”
Contact your local gas supplier if you are not sure about the inlet pressure.
BURNER INPUT REQUIREMENTS:
Input ratings shown on the model/serial rating plate are for elevations up to 2,000 ft (609.6 m).
For elevations above 2,000 ft (609.6 m), ratings are reduced at a rate of 4% for each 1,000 ft
(304.8 m) above sea level (not applicable for Canada).
GAS SUPPLY PRESSURE TESTING:
Line pressure testing above ½ psi gauge (14" WCP):
The range and its individual shutoff valve must be disconnected from the gas supply piping
system during any pressure testing of that system at test pressures in excess of ½ psi (3.5
kPa).
Line pressure testing at ½ psi gauge (14" WCP) or lower:
The range must be isolated from the gas supply piping system by closing its individual
manual shutoff valve during any pressure testing of the gas supply piping system at test
pressures equal to or less than ½ psi (3.5 kPa).