AE & AEK Series Communication Protocol

Attention
When use RS232 / 485 to control AE/AEK series SMPS, user must follow the rules as stated
below.
A: Before entering the power-on command (POWER 1, GLOB 1), it is recommended to set /
check the voltage and current value in advance before power on. After receiving the
response from SMPS, user may then assign power-on command.
B: All characters of RS232/485 must be transmitted completely between 400ms according
CR LF (0D0A). Transmitting the characters over the time range stated, system will ignore
the command.
C: After shut down power input, all setting commands will return to initial value when output
voltage drop (or set) to 0V. At this time, the status resumes to LOCAL MODE.
D: Via GUI, user may control up to 8 SMPS (ADDS0-7) max. Please check the SMPS
Address set is not conflicted when connecting multiple SMPS simultaneously.
E: To set/query multiple SMPS in remote mode via protocol, user must assign the address of
each SMPS by entering command ADDS x (x=0~7); otherwise, the SMPS will not be able to
set/query. If customer uses only one SMPS, it will not be necessary to set address