Product Manual

42
Example2
When user setting value= Disable, the SD-series “Output frequency” is
within the range of 47 Hz~63 Hz, the internal transfer relay will close.
Default= 7Hz
Model
Setting value range
110 V
0 ~ 7 Hz
230 V
0 ~ 7 Hz
Table 37. Sync Frequency <FUNC8>
10. Overload Alarm <FUNC9>Set the overload alarm. When the SD-series
output power is higher than the set value, the SD-series will sound a “beep”
to remind you that the unit is going to shut-down. At the same time, the
internal Dry Contact Relay will open/close.
Default = 104%
Setting range = 50%~110%
11. Shut-down retry <FUNC10>When SD-series is shut-down under OVP, UVP,
Overload or short circuit conditions, the inverter will automatically try to
restart according to below
Protection type
Retry default
Setting value Range
OLP
Short-circuit protection
5 times after protection
0~15 times
OVP
UVP
Auto-recovery continuously
N/A
Table 38. Shut-down retry <FUNC10>
12. Saving Level <FUNC11>Setting the SD-series to power saving to reduce
consumption from the batteries.
Default = 0
Setting range = 0 ~ 7
Setting Value
Status
0
Default
1
2%
2
3%
3
4%
4
5%
5
6%
6
7%
7
8%
Table 39. Saving Level <FUNC11>