SD Series User’s Manual EN [Page 3] FR [Page 47] SD1500/2500/3500 PURE SINE WAVE INVERTER SD1500/2500/3500 Signal de sortie sinusoïdal pur
Legal Provisions Copyrights 2017 COTEK Electronic IND. CO. All Rights Reserved. Any part of this document may not be reproduced in any form for any purpose without the prior written permission of COTEK Electronic IND. CO. For the conditions of the permission to use this manual for publication, contact COTEK Electronic IND. CO., LTD. In all related COTEK product activities, Neither COTEK Electronic IND. CO., LTD.
Table of Content 1. IMPORTANT SAFETY INFORMATION 1 1-1. General Safety Precautions 1 1-2. Precautions When Working with Batteries 1 1-3. Installation 2 2. FUNCTIONAL CHARACTERISTICS 3 2-1. General Information 3 2-2. Application 3 2-3. Electrical Performance 4 2-4. Mechanical Drawings 10 3. INTRODUCTION 12 3-1. Power ON / OFF / REMOTE (Main) switch 13 3-2. LED Indicator 13 3-3. DIP Switch (S1~S8) Assignment 14 3-4. DC Input - (please refer to DC wiring connections on P.20) 15 3-5.
. DC WIRING CONNECTIONS 20 4-1. DC Input Terminals 21 4-2. Hard-wire Installation 22 5. PARALLEL MODE 28 5-1. Prepare for Parallel Usage 28 5-2. Industry Applications 29 5-3. Wiring for Parallel Usage 31 5-4. AC Wiring Diagram 33 5-5. Remote command for the parallel connection 37 5-6. Remove Parallel Connection 37 6. RS-232 COMMAND 6-1. RS-232 command introduction 38 38 7. TROUBLESHOOTING 46 8.
1. Important Safety Information WARNING! Before using the inverter, read and save the safety instructions. 1-1. General Safety Precautions 1-1-1. Do not expose the Inverter to rain, snow, spray, bilge or dust. To reduce risk of hazard, do not cover or obstruct the ventilation openings. Do not install the inverter in a zero-clearance compartment. Overheating may take place. 1-1-2.
EN 1-3. Installation The power inverter should be installed in a location that meets the following requirements: Dry – Do not allow water to drip or splash on the inverter. Cool – Ambient air temperature should be between -20℃ and 50℃, but he cooler the better. Safety – Do not install batteries in the compartment or other areas here flammable fumes existence such as fuel storage areas or engine compartments. Ventilated – Allow at least one feet of clearance around the Inverter for air flow.
2. Functional Characteristics 2-1. General Information SD-series is new generation power inverter equipped with N+1 parallel power function , 3-phase capability, and AC transfer switch. SD series is suitable for RV, Marine and Emergency appliances.
EN 2-3. Electrical Performance 2-3-1. SD1500 Specification MODEL SD1500-112 SD1500-124 SD1500-148 SD1500-212 SD1500-224 SD1500-248 Output Rating Power 1500VA (de-rating after 40°C, refer to de-rating curve) Output Power (Max. 3 min.) Peak Power (Max. 3 sec.) Surge Power (Max. 0.2 sec.) 1500~1800VA 1800~2400VA >2400VA Waveform Pure Sine Wave Efficiency (Max.) Output Voltage (@rated VDC) 88% 89% 90% 100 / 110 / 115 / 120VAC ± 3% Output Frequency 50 / 60Hz ± 0.
MODEL Output Protection SD1500-112 SD1500-124 SD1500-148 SD1500-212 SD1500-224 SD1500-248 Short Circuit / Overload / Over Temperature / Over Voltage Protection Environment Working Temp. -20~+60°C; refer SD1500 power de-rating curve Storage Temp. -40~+70°C Relative Humidity Max.
EN 2-3-2. SD2500 Specification MODEL SD2500-112 SD2500-124 SD2500-148 SD2500-212 SD2500-224 SD2500-248 Output Rating Power 2500VA (de-rating after 40°C, refer to de-rating curve) Output Power 2500~3000VA (Max. 3 min.) Peak Power 3000~4000VA (Max. 3 sec.) Surge Power >4000VA (Max. 0.2 sec.) Waveform Pure Sine Wave Efficiency (Max.) Output Voltage 88% 89% 90% 100 / 110 / 115 / 120VAC ± 3% (@rated VDC) 88% 88% 90% 200 / 220 / 230 / 240VAC ± 3% Output Frequency 50 / 60Hz ± 0.
MODEL SD2500-112 SD2500-124 SD2500-148 SD2500-212 SD2500-224 SD2500-248 Input Protection Reverse Polarity (Fuse) / Under Voltage / Over Voltage Protection / AC over current (Breaker) Output Protection Short Circuit / Overload / Over Temperature / Over Voltage Protection Environment Working Temp. -20~+60°C; refer SD2500 power de-rating curve Storage Temp. -40~+70°C Relative Humidity Max.
EN 2-3-3. SD3500 Specification MODEL SD3500-112 SD3500-124 SD3500-148 SD3500-212 SD3500-224 SD3500-248 Output 3500W (de-rating after 35°C, refer to de-rating curve for 12V) (de-rating after 40°C, refer to de-rating curve for 24V and 48V) Rating Power Output Power (Max. 3 min.) Peak Power (Max. 3 sec.) Surge Power (Max. 0.2 sec.) 3500~4500 W 4500~6000 W >6000 VA Waveform Pure Sine Wave Efficiency (Max.
MODEL SD3500-112 SD3500-124 SD3500-148 SD3500-212 SD3500-224 SD3500-248 Input Protection Reverse Polarity (Fuse) / Under Voltage / Over Voltage Protection / AC over current (Breaker) Output Protection Short Circuit / Overload / Over Temperature / Over Voltage Protection Environment Working Temp. -20~+60°C; refer SD3500 power de-rating curve Storage Temp. -40~+70°C Relative Humidity Max.
EN Figure 2. SD2500 de-rating curve Figure 3. SD3500 de-rating curve Mode / Transfer Switch Haphazard Normal Exacting Online SD Series Transfer-Time Table ATS STS Frequency is synchronized: < 4ms.; Inverter to utility AC: 8~10ms.; Frequency is not synchronized: Utility AC to inverter: 16~50ms. Inverter to utility AC: < 4ms.; Utility AC to inverter: 16~50ms. Inverter to utility AC: 8~10ms.; < 4ms Utility AC to inverter: 16~25ms. Inverter to utility AC: 8~10ms.; Inverter to utility AC: < 4ms.
2-4. Mechanical Drawings Figure 4. SD series mechanical drawings Model A (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm) SD1500 351 160 93.1 268.6 8.5 11.5 128 283 SD2500 436 240.0 95.6 268.6 8.5 11.5 128 283 SD3500 496 240.0 125.6 268.6 8.5 11.5 128 283 Table 2.
EN 3. Introduction 【Version 1】General Model Figure 5. SD general model front panel 【Version 2】UL Model Figure 6. SD UL model front panel Figure 7.
Front Panel / Rear Panel 1 Power ON/OFF/REMOTE (Main) switch 10 AC output socket 2 Status LED 11 Reset Button 3 Dip Switch (S1~S8) 12 CAN2 Port (only to be used in parallel mode) 4 DC Input - 13 CAN1 Port (only to be used in parallel mode) 5 DC Input + 14 6 Chassis Ground 15 Green terminal (Remote and Parallel select) 7 AC Output 16 Remote / RS-232 port 8 By-pass AC Input 17 FAN 9 AC input circuit breaker LCM Port (Connection for LCD remote control panel) Table 3.
EN 3-3. DIP Switch (S1~S8) Assignment 1=ON/0=OFF Figure 8. DIP switch (S1~S8) PIN# PIN Assignment 1 AC output voltage setting 2 AC output voltage setting 3 AC output frequency setting 4 To set-up 3 Phase output or Energy-saving level 5 To set-up 3 Phase output or Energy-saving level 6 To set-up 3 Phase output or Energy-saving level 7 To set-up DIP Switch S4~S6 for power saving or 3 Phase output 8 To set-up function parameters adjustment via LCM port or DIP switch Table 5.
B. Power device leaving saving mode(re-start) Restart threshold = rate power x setting % x 2~3 In case the power over the restart threshold, the power device will re-start and provide the AC power.
EN 3-5. DC Input + (please refer to DC wiring connections on P.20) 3-6.Chassis Ground:Connect the wire # 8 AWG to vehicle chassis WARNING! Operating the inverter without a proper ground connection may cause electrical safety hazard. 3-7. AC Output (Please refer to hard wiring installation on P.22) 3-8. By-pass AC input (please refer to hard wiring installation on P.22) 3-9. AC input circuit breaker The AC input circuit breaker protects the model from overload.
WARNING! LCM port is for remote control connection only. Please make sure the connection is correct. (CAN cable to CAN1 / CAN2 port , Remote cable to LCM port) If CAN cable is connected to LCM port, or vice versa, the inverter will be damaged. 3-13. LCM Port Connection for LCD remote control panel, you can set and display the SD-series operation status. Figure 10. LCM port Figure 11. LCM cable LCD Remote Control Panel SD Series PIN Num. Signal Description PIN Num.
EN 3-14. Green terminal (Remote and Parallel select) Figure 12. Green terminal PIN # 1 2 3 4 5 PIN Assignment GND -ENB ENB Parallel Jump Parallel Jump Table 12. Green terminal PIN assignment 3-14-1. Parallel Jump Function (please refer to section 5 for further detailed info.) 1. Before installing the inverter, you need to ensure the main switch is in the OFF position. 2. Use 20 ~ 24 #AWG wire to connect the parallel jump terminal. 3-14-2. Remote Control Function 1.
3-15. RS-232 Port RS-232 Port:Serial port monitoring and control through computer’s interface. Figure 14. RS-232 port Figure 15. RS-232 cable SD Series Computer PIN Num. Signal Description PIN Num. Signal Description 1 Not used 1 Not used 2 GND 5 GND 3 RXD 3 TXD 4 TXD 2 RXD 5 Not used Not used 6 Not used Not used Table 13. The connection between SD series and computer The connection between this SD-series and the computer is as follows: Figure 16.
EN 4. DC Wiring Connections Follow the instructions to connect the battery cables to the DC input terminals of the Inverter. The cable should be as short as possible (less than 6 feet / 1.8 meters ideally) so that it can handle the required current in accordance with the electrical codes or application regulations. Inappropriate length of cables will reduce the inverter performance such as poor surge capability, frequent low-input voltage warnings, and shut-down.
Do not place anything between battery cable lug and terminal surface. Assemble exactly as shown. Figure 17. Battery cabling WARNING! During the first installation, a small spark is a normal phenomenon because the internal capacitors charging. Do not be concerned. 4-1. DC Input Terminals Connect DC input terminals to 12V / 24V / 48V battery or other power sources. [ + ] represents positive, [ - ] represents negative.
EN 4-2. Hard-wire Installation 4-2-1. SD series provides the flexibility of hard-wire connection, and this function will make external control panel wiring easier. 【Version 1】General model Step 1. Remove the four screws of AC wiring compartment and pull it out with care. Figure 18. General model setting─Step 1 Step 2. Pull the line through the snap bushing of the AC wiring compartment cover then follow below picture operation. Figure 19.
Note The only difference between 110V and 220V is within the AC Input breaker L or N and thus will not affect the wiring configuration. Note In case that user wants to install the earth-leakage circuit breaker, COTEK recommend time delay type. The major specification of the circuit breaker is as following: Earth-leakage current:100mA, 300mA, 500mA Time:0.45 second, 1 second, 2 seconds Recommend model:NV50-SN, Time delay type of Shihin Electric 【Version 2】UL model Step 1.
EN Figure 23. UL model setting─AC wiring Step 3. Use the screwdriver to fix the cover. Figure 24. UL model setting─Step 3 4-2-2. Connect AC output and AC input wiring to the SD series terminals. Please take the following information as your reference. Terminal AC OUTPUT AC INPUT Wire Color Line (L) Black Neutral (N) White Line (L) Brown Neutral (N) Blue Ground Green / Yellow or Bare copper Table 17.
4-2-3. Neutral Grounding Connection Setting (For SD1500 Only) The default setting is option A: NO ONNECTION BETWEEN NEUTRAL CONDUCTOR (N) OF THE AC OUTPUT AND SAFETY GROUND (PE/GND) CAUTION! It is advised that all the electrical installation should conform to the local electrical codes and should be carried out by a certified technician.
EN chassis of the inverter is connected to the earth ground, the “N” terminal of the AC output will not be grounded (bonded) to the earth ground. Under this condition, the “N” terminal of the AC output will not be a Neutral in the true sense.
Note In case the load current over the outlet rated current, please use the hard wire terminal next to the outlets. Note Recommend GFCI connector: HUBBELL INC WIRING DEVICE DIV, Type GF20 and GFRST20. Rated 125V, 20A COOPER WIRING DEVICES, Type VGF20 and SGF20. Rated 125V, 20A LEVITON MFG CO INC, Type 7899-W and GFNT2. Rated 125V, 20A PASS & SEYMOUR INC, Type 2097. Rated 125V, 20A WARNING! When using full power, it is recommended to use the wiring terminal.
EN 5. Parallel Mode 5-1. Prepare for Parallel Usage 1. Before setting, you need to ensure that the main switch is ”OFF”. 2. Before using the parallel function, you need to set the parallel jump of the green terminal the status of which must be “ON”, if the between in another SD is set to ”OFF” which is termination resistors. Figure 26. Parallel jump setting Example:If three SD inverters are paralleled, setup green terminal.
Note Please select one unit to be Master unit. Use the cables to connect Master and Slave units. The CAN1 and CAN2 port connection please refer to Figure 25. Note The simple method to determine the terminal resistor:No need to set the terminal resistor when CAN1 and CAN2 port have wiring. Note SD series can be used for N+1 (N≦4) redundancy and the ability of enlarge the capacity (Users can install maximum 5 units of inverters together in parallel in order to provide the power expansion). 3.
EN 1Φ2W Type 1Φ3W 3Φ4W Waveform Battery Set up Warning Transfer Switch STS module:Single < 4ms; N+1 & 1P3W & 3P4W < 6ms Do not support N+1 operation, maximum of two SD inverters, THD < 4% Do not support N+1 operation, maximum of three SD inverters, THD < 4% DIP switch (S7) must be set to “1” DIP Switch Setting Wiring Diagram Refer to 5-2-1. / 5-2-2. Refer to 5-2-3. Refer to 5-2-4. Refer to Figure 32. / Figure 33. Refer to Figure 34. Refer to Figure 35. Table 20.
5-2-2. 1Φ2W Switch Table ─ Auto Master Auto Master S4 0 S5 0 S6 0 S7 0 S8 1 Table 22. 1Φ2W switch table ─ auto master 5-2-3. 1Φ3W Switch Table Master Slave 180° S4 0 0 S5 0 1 S6 0 1 S7 1 1 S8 1 1 Table 23. 1Φ3W switch table 5-2-4. 3Φ4W Switch Table L1 Master L2 -120° Slave L2 +120° Slave S4 0 1 1 S5 0 0 0 S6 0 0 1 S7 1 1 1 S8 1 1 1 Table 24. 3Φ4W switch table 5-3. Wiring for Parallel Usage 5-3-1. Connection method 1.
EN Figure 29. Connection Diagram_2 Figure 30.
5-4. AC Wiring Diagram Figure 31. SD series front panel introduction 【1Φ2W ─ Wiring Diagram】 Figure 32.
EN 【1Φ2W Auto Master ─ Wiring Diagram】 Figure 33. 1Φ2W parallel AC wiring diagram ─ auto master Note Auto master can be operated under 1Φ2W mode. Under 1Φ2W auto master mode, please set up the inverter by Ethernet or Remote control CR-10. Note 1Φ2W system parallel Max. N+1=5 Note If you parallel N units, the first (unit 1) and the last unit (unit N) must set parallel jumper in ON position.
【1Φ3W ─ Wiring Diagram】 Figure 34.
EN 【3Φ4W ─ Wiring Diagram】 Figure 35. 3Φ4W parallel AC wiring diagram Model Connection / 100V 110V 115V 120V 200V 220V 230V 240V L1-to-L2 173 191 199 208 346 381 398 416 L2-to-L3 173 191 199 208 346 381 398 416 SD L3-to-L1 173 191 199 208 346 381 398 416 Series L1-to-N 100 110 115 120 200 220 230 240 L2-to-N 100 110 115 120 200 220 230 240 L3-to-N 100 110 115 120 200 220 230 240 Output VAC Table 25.
5-5. Remote command for the parallel connection There are two ways for parallel connection remote setting:1. RS-232, 2. CAN-Bus. The RS-232 communication protocol not support broadcast function. In case of the remote control use the RS-232 port, please follow the setting steps for the SD setting. RS-232 remote communication setting: 1. Select one SD to be the Master and follow the setting: Scenario S1 S2 S3 S4 S5 S6 S7 S8 Master X X X 0 0 0 1 X Table 26.
EN 6. RS-232 Command 6-1. RS-232 command introduction 6-1-1. RS-232 command: Command format: This unit uses high-level language commands with a CR (0DH) and LF (0AH) as the end of the command. The system would interpret and execute the command only after these two characters are received. After the unit execute the command, it would send a response string to the computer.
6-1-3.
EN 2. OVP Recovery :When the DC input voltage is higher than the OVP setting, the SD-series shuts-down; once the input voltage falls below the set OVP value, the SD-series will automatically restart. Default = 15 VDC @ 12V Model, 30 VDC @ 24V Model, 60 VDC @ 48V Model Model Setting value range 12 V 13 VDC ~ 15 VDC 24 V 26 VDC ~ 30 VDC 48 V 52 VDC ~ 60 VDC Table 30. OVP Recovery 3. UVP Setting :Setting Under Voltage Protection (UVP) and Shut-down on the inverter operation.
Note The value of the voltage set for the “UV Alarm” should be equal to or higher than the value set for “UVP” or else the unit will shut-down without any audible warning. 6. O/P Voltage :Setting the SD-series output voltage on the inverter operation. Default = 110 VAC @ 110 V Model, 230 VAC @ 230 V Model Model Setting value range 110 V 97 VAC ~ 123 VAC 230 V 194 VAC ~ 246 VAC Table 34. O/P Voltage 7.
EN Example2: When user setting value= Disable, the SD-series “Output frequency” is within the range of 47 Hz~63 Hz, the internal transfer relay will close. Default= 7Hz Model Setting value range 110 V 0 ~ 7 Hz 230 V 0 ~ 7 Hz Table 37. Sync Frequency 10. Overload Alarm :Set the overload alarm. When the SD-series output power is higher than the set value, the SD-series will sound a “beep” to remind you that the unit is going to shut-down.
14. Bypass Relay :The setup is provided in one of the following two ways. On-line Mode or Off-line Mode ( Exacting, Normal, Haphazard). Default = Normal (Off line). Mode SETT Transfer Relay Switching Feature a. The transfer relay will switch “ON” Haphazard 0 Conformance to voltage and frequency b. The transfer relay will switch “OFF” Conformance to voltage or frequency a. The transfer relay will switch “ON” Normal 1 Conformance to voltage , frequency and phase b.
EN Mode / Transfer Switch Haphazard Normal Exacting Online SD Series Transfer-Time Table ATS STS Frequency is synchronized: < 4ms.; Inverter to utility AC: 8~10ms.; Frequency is not synchronized: Utility AC to inverter: 16~50ms. Inverter to utility AC: < 4ms.; Utility AC to inverter: 16~50ms. Inverter to utility AC: 8~10ms.; < 4ms Utility AC to inverter: 16~25ms. Inverter to utility AC: 8~10ms.; Inverter to utility AC: < 4ms.; Utility AC to inverter: 16~50ms. Utility AC to inverter: 16~50ms.
18. Alert Setting :When alert occurs, the internal dry contact relay will open/close. Default = Alert, SHDN Setting range = 0~3 Setting Menu Buzzer Setting SETT (RS-232) Alert (LCD) 0 Disable 1 SHDN 2 Alert 3 Alert , SHDN Table 45. Alert Setting 19. Language :The SD-series have different languages available and are selectable.
EN 7. Troubleshooting Problems and Symptoms A. Power status red light is blinking fast. B. Power status red light is Blinking slowly. Possible Cause Over input voltage. (OVP) Low input voltage. (UVP) Solutions Check input voltage. Reduce input voltage. Recharge battery. Check connections and cables. Improve ventilation. Make sure C. Power status red light is blinking Intermittently. Thermal shut-down. (OTP) ventilation, shafts of the inverter are not obstructed. Lower ambient temperature.
Dispositions légales Copyrights 2016 COTEK Electronic IND. CO. tous droits réservés. Aucune partie de ce document ne peut être reproduite, quelle qu’en soit la manière et quel qu’en soit le but, sans autorisation préalable écrite de COTEK Electronic IND. CO. Pour obtenir l’autorisation de publier ce manuel, adressez-vous directement à COTEK Electronic IND. CO., LTD. Pour l’ensemble des activités COTEK, ni COTEK Electronic IND. CO., LTD.
FR Table des matières 1. CONSIGNES DE SÉ CURITÉ 1-1. Consignes de sécurité 50 1-2. Précautions avec les batteries 50 1-3. Installation 51 2. CARACTÉ RISTIQUES FONCTIONNELLES 52 2-1. Système 52 2-2. Applications 52 2-3. Performances électriques 53 2-4. Schémas d’encombrement 60 3. INTRODUCTION 48 50 61 3-1. Interrupteur ON / OFF / REMOTE 62 3-2. Témoins lumineux à DEL 62 3-3. Interrupteurs DIP 63 3-4. Négatif (-) entrée courant continu 65 3-5.
3-17. Protections 69 4. CONNEXIONS COURANT CONTINU (ALIMENTATION DE L’ONDULEUR) 70 4-1. Entrées courant continu 71 4-2. Connexion fixe (câblage) 72 5. MODE PARALLÈ LE 77 5-1. Préparation 77 5-2. Applications Industrielles 78 5-3. Câblage 80 5-4. Connexions courant alternatif 82 5-5. Commande déportée des onduleurs montés en parallèle 86 5-6. Déposer les connexions de montage en parallèle 86 6. PROTOCOLE RS-232 87 6-1. Introduction au protocole RS-232 87 7.
FR 1. Consignes de sécurité Attention ! Prendre le temps de lire les consignes de sécurité avant d’utiliser l’onduleur. 1-1. Consignes de sécurité 1-1-1. Ne pas exposer l'onduleur à la pluie, à la neige, aux projections d'eau ou à la poussière. Pour réduire les risques électriques (incendie) ne pas couvrir ni obstruer les grilles de ventilation. Ne pas installer l'onduleur dans un compartiment non aéré au risque de provoquer une surchauffe. 1-1-2.
1-3. Installation Sec ─ Ne pas exposer l’onduleur au ruissellement ou aux projections d’eau. Frais ─ La température ambiante de l’air doit être comprise entre 0°C et 33°C. Le plus frais étant préférable. Sû r ─ Ne pas installer l'onduleur à proximité des batteries ou dans un compartiment où peuvent se produire des émanations inflammables tel que le compartiment de stockage des combustibles ou le compartiment moteur.
FR 2. Caractéristiques fonctionnelles 2-1. Système Les onduleurs de la série SD font partie de la dernière génération d’onduleurs acceptant un montage en parallèle (redondance N+1), compatible avec une alimentation triphasée. Ils sont équipés d’un relais de transfert et conviennent aux véhicules de loisirs, bateaux de plaisance et équipements de secours. Caractéristiques Conception permettant un montage en parallèle.
2-3. Performances électriques 2-3-1.
FR Modèle SD1500-112 SD1500-124 SD1500-148 SD1500-212 SD1500-224 SD1500-248 Environnement Plage de Températures, Fonctionnement Plage de Températures, Stockage Humidité Relative -20 à +60 °C, voir courbes de déclassement du SD2500 -40 à +70 °C 90 % maximum, sans condensation Normes de Sécurité et Compatibilité É lectromagnétique UL 458 Sécurité ---- EN 62368-1 (connexion par câbles uniquement) CEM FCC Class B EN 55032, EN 55024 ---- CISPR 25; ISO 7637-2 Marquage CE Panneaux de Contrô le et In
2-3-2.
FR Modèle SD2500-112 SD2500-124 SD2500-148 SD2500-212 SD2500-224 SD2500-248 Environnement Plage de Températures, Fonctionnement Plage de Températures, Stockage Humidité Relative -20 à +60 °C, voir courbes de déclassement du SD2500.
2-3-3.
FR Modèle SD3500-112 SD3500-124 SD3500-148 SD3500-212 SD3500-224 SD3500-248 Environnement Plage de Températures, Fonctionnement Plage de Températures, Stockage Humidité Relative -20 à +60 °C, voir courbes de déclassement du SD3500.
Courbes de déclassement Schéma 1. SD1500 – Courbes de déclassement Schéma 2. SD2500 – Courbes de déclassement Schéma 3.
FR 2-4. Schémas d’encombrement Schéma 4. Série SD – Schémas d’encombrement Modèle A (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm) SD1500 351 160,0 93,1 268,6 8,5 11,5 128 283 SD2500 436 240,0 95,6 268,6 8,5 11,5 128 283 SD3500 496 240,0 125,6 268,6 8,5 11,5 128 283 Tableau 2.
3. Introduction Modèle standard Schéma 5. Série SD – Vue du panneau avant Version UL Schéma 6. Série SD modèles UL – Vue du panneau avant Schéma 7.
FR Présentation 1 Interrupteur On/Off/REMOTE (panneau déporté) 10 Sortie CA 2 DEL d’état 11 Bouton Reset (réinitialisation) 3 Interrupteurs DIP (S1-S8) 12 Port CAN2 (utilisé si montage en parallèle) 4 Entrée négatif CC (-) 13 Port CAN1 (utilisé si montage en parallèle) 5 Entrée positif CC (+) 14 6 Borne de masse (GND) 15 7 Sortie CA 16 Port RS-232 (connexion du panneau déporté) 8 By-pass entrée CA 17 Ventilateur 9 Disjoncteur, entrée CA Port LCM (connexion panneau déporté ave
3-3. Interrupteurs DIP (S1-S8) 1=ON / 0=OFF Schéma 8.
FR A. Entrée en mode économie d’énergie Puissance nominale x % paramétré = seuil de basculement en mode économie d’énergie. Si la charge est inférieure au seuil durant 5 secondes, l’onduleur bascule en mode économie d’énergie. B. Sortie du mode économie d’énergie Puissance nominale x % paramétré x 2-3 = seuil de sortie du mode économie d’énergie. Lorsque la charge est supérieure au seuil paramétré, l’onduleur sort du mode économie d’énergie.
3-3-4. S8, paramétrage via interrupteur DIP ou LCM Paramètre S8 LCM 0 Interrupteur DIP 1 1=ON / 0=OFF Tableau 9. Sélection du mode de paramétrage 3-4. Négatif (-) entrée courant continu (voir chapitre 4, connexions courant continu) 3-5. Positif (+) entrée courant continu (voir chapitre 4, connexions courant continu) 3-6.
FR 3-12. Ports CAN1 et CAN2 (pour montage en parallèle uniquement) Schéma 9. Ports CAN1 et CAN2 1. Pour un montage en parallèle, s’assurer que le cavalier sur le bornier vert est paramétré sur ON. 2. Utiliser un câble RJ-45 pour raccorder les onduleurs entre eux : ports CAN1 (CAN2) à ports CAN1 (CAN2).
3-13. Port LCM Connecteur du panneau déporté avec afficheur LCD. Schéma 10. Port LCM Schéma 11. Câble LCM Panneau déporté Onduleur SD Broche Signal Broche 1 CANH 1 2 CANL 2 3 PON 3 4 VCC- 4 5 VCC+ 5 6 DIS 6 7 5VS- 7 8 5VS+ 8 Tableau 11. Connecteur panneau déporté – Broches et description du signal Note Les câbles doivent être le plus court possible (longueur inférieure à 10 mètres) pour que le signal soit correct. 3-14.
FR 3-14-1. Cavalier – Mode parallèle (voir chapitre 5 pour plus de détails) 1. Avant d’installer l’onduleur, s’assurer que l’interrupteur est sur OFF. 2. Utiliser un conducteur dont la section est comprise entre 0,5 mm² et 0,25 mm² pour cette connexion. 3-14-2. Mode commande déportée 1. Avant d’installer l’onduleur, s’assurer que l’interrupteur est sur OFF. 2. Pour utiliser l’onduleur dans ce mode, placer l’interrupteur en position REMOTE (commande déportée). 3.
Broche Signal Broche Signal 1 Non utilisé 1 Non utilisé 2 GND (masse) 5 GND (masse) 3 RXD (réception données) 3 TXD (transmission données) 4 TXD (transmission données) 2 RXD (réception données) 5 Non utilisé Non utilisé 6 Non utilisé Non utilisé Tableau 13. Connexions onduleur SD/ordinateur La connexion entre onduleur SD et ordinateur se présente comme suit: Schéma 16. Connexion onduleur SD / ordinateur 3-16.
FR 4. Connexions courant continu (alimentation de l’onduleur) Les câbles de connexion à la batterie doivent être le plus court possible (idéalement, la longueur devrait être inférieure à 1,80 m) et de section suffisante pour réaliser une installation conforme aux normes en vigueur. Les câbles de section insuffisante ou trop longs provoqueront une perte de performances (faible capacité en pointe, alarmes tension basse et extinctions de l’onduleur répétées).
Ne rien placer entre la cosse à œil et le contact sur la borne. Procéder comme indiqué sur le schéma. Schéma 17. Câblage batterie AVERTISSEMENT ! Lors de la mise en service initiale, une étincelle peut se produire car les condensateurs internes se chargent. Ceci est un phénomène normal. 4-1. Entrées courant continu Raccorder les bornes d’entrée courant continu à une batterie 12 V, 24 V ou 48 V ou à une autre source courant continu. [+] correspond à la borne positive et [-] à la borne négative.
FR 4-2. Connexion fixe (câblage) 4-2-1. Sur les onduleurs de la série SD, il est possible de réaliser une connexion fixe. Cela rend plus aisé le câblage du panneau déporté. 【Modèle standard】 É tape 1. Déposer les 4 vis sur la sortie CA. Schéma 18. É tape 1 – Modèle standard É tape 2. Passer le câble dans le presse-étoupe et suivre les instructions de câblage des schémas ci-dessous. Schéma 19. É tape 2 – Modèle standard Systèmes 100 V CA~120 V CA / 200 V CA~240 V CA Schéma 20.
Note Si l’installation requiert une protection différentielle, COTEK recommande d’installer un disjoncteur avec temporisation. Courant de fuite : 30 mA, 100 mA, 300 mA, 500 mA Temporisation : 0,45 seconde, 1 seconde, 2 secondes 【Modèle UL】 É tape 1. Déposer les 4 vis sur la sortie CA. Schéma 21. É tape 1 – Modèle UL É tape 2. Passer le câble dans l’anneau et suivre les instructions de câblage des schémas ci-dessous. Schéma 22. É tape 2 – Modèle UL Schéma 23.
FR É tape 3. Reposer les vis. Schéma 24. É tape 3 – Modèle UL 4-2-2. Détail des connexions courant alternatif Borne Sortie CA Entrée CA Couleur Phase (L) Noir Neutre (N) Blanc Phase (L) Marron Neutre (N) Bleu Terre (GND) Longueur et section du câble Vert/Jaune ou cuivre nu Tableau 17.
4-2-3. Connexion du neutre La configuration par défaut est « A » : pas de connection du neutre (N) de la sortie CA à la terre (PE/GND). Schéma 25. Options SD1500 Attention ! L’installation doit être effectuée par un électricien qualifié, conformément aux normes locales en vigueur.
FR 4-2-4. Socles disponibles et caractéristiques Il est possible d’utiliser la sortie CA et les bornes de sortie CA étant données qu’elles sont reliées en parallèle. Type Nombre de sorties Tension Courant (V CA) (A) GFCI 2 125 20 NEMA 2 125 15 Europe 1 250 16 1 250 15 U.K. 1 250 13 Bornier 1 100~250 35 ① UL458 1 120 35 ② Universel 1 100~250 16 Australie/ Nlle Zélande ① UL458 sur modèles 112 et 124 exclusivement.
5. Mode Parallèle 5-1. Préparation 1. S’assurer que l’interrupteur est sur OFF. 2. Paramétrer le cavalier (mode parallèle) du bornier vert sur ON sur le premier et sur le dernier onduleur (paramétrer les autres cavaliers sur OFF). Schéma 26. Paramétrage du cavalier Exemple:paramétrage du bornier vert pour le montage en parallèle de troix onduleurs SD.
FR Note Déterminer quel onduleur sera le maître. Raccorder les onduleurs esclaves à l’onduleur maître. Pour la connexion des ports CAN1 et CAN2, voir schéma 27. Note Il n’est pas nécessaire de monter une résistance de terminaison lorsque CAN1 et CAN2 sont câblés. Note Afin d’augmenter la puissance, il est possible de monter au maximum 5 onduleurs de la série SD en parallèle : N+1 (N≦4). 3. Paramétrer la tension et la fréquence via les interrupteurs DIP sur chaque onduleur (voir paragraphe 3-3). 4.
Type 1 phase 2 fils 1 phase 3 fils 3 phases 4 fils Forme du signal Connexion batterie Module de transfer STS: Monophasé < 4 ms; N+1 & 1 phase 3 fils & 3 phases 4 fils < 6 ms Attention Maximum deux onduleurs SD en parallèle. DHT < 4% Maximum trois onduleurs SD en parallèle. DHT < 4% L’interrupteur DIP S7 doit être positionné sur 1 pour cette configuration. Inter.. DIP Voir § 5-2-1. / 5-2-2. Voir § 5-2-3. Voir § 5-2-4. Câblage Voir schéma 32. / schéma 33. Voir schéma 34. Voir schéma 35.
FR 5-2-2. 1 phase 2 fils ─ Auto Master (reconnaissance automatique onduleur maître) Auto Master S4 0 S5 0 S6 0 S7 0 S8 1 Tableau 22. 1 phase 2 fils ─ Auto Master – Configuration des interrupteurs DIP 5-2-3. 1 phase 3 fils – Configuration des interrupteurs DIP Maître Esclave 180° S4 0 0 S5 0 1 S6 0 1 S7 1 1 S8 1 1 Tableau 23. 1 phase 3 fils – Configuration des interrupteurs DIP 5-2-4.
Schéma 29. Schéma de câblage_2 Schéma 30.
FR 5-4. Connexions courant alternatif Schéma 31. Série SD – Présentation du panneau avant 【1 phase 2 fils ─ Schéma de câblage】 Schéma 32.
【1 phase 2 fils Auto Master ─ Schéma de câblage】 Schéma 33. 1 phase 2 fils – Câblage CA pour un montage en parallèle en mode Auto Master Note La reconnaissance automatique de l’onduleur maître (Auto master) peut fonctionner avec un câblage 1 phase 2 fils en paramétrant l’onduleur SD via un réseau Ethernet ou un panneau déporté type CR-10. Note Pour un montage en parallèle via un câblage 1 phase 2 fils, relier entre eux 5 onduleurs maximum (Max. N+1=5).
FR 【1 phase 3 fils ─ Schéma de câblage】 Schéma 34.
【3 phases 4 fils ─ Schéma de câblage】 Schéma 35.
FR 5-5. Commande déportée des onduleurs montés en parallèle Il y a deux manières de paramétrer la commande déportée:via le protocole RS-232 ou CAN bus. Le protocole RS-232 n’est pas compatible avec un montage en parallèle. Si la commande déportée est raccordée via le port RS-232, suivre les instructions de paramétrage ci-dessous. Configuration du port RS-232: 1. Sélectionner un onduleur SD comme maître et le configurer comme indiqué ci-dessous.
6. Protocole RS-232 6-1. Introduction au protocole RS-232 6-1-1. Format des commandes RS-232 Chaque commande commence par un code CR (0DH) et se termine par un code LF (0AH). Le système ne peut interpréter et exécuter une commande qu’une fois avoir reçu ces deux codes. Il retourne alors une réponse à l’ordinateur, qui peut se présenter comme suit : = > CR LF : Command executed successfully? > CR LF : Command error, not accepted! > CR LF : Command correct but execution error (ex : parameters out of range).
FR 6-1-3.
6-1-4. Détails des paramètres 1. – OVP Setting – Coupure tension haute Valeur par défaut : 16 V CC @ 12 V – 32 V CC @ 24 V – 64 V CC @ 48 V Modèle Plage de valeurs admissibles 12 V 15 V CC – 16 V CC 24 V 30 V CC – 32 V CC 48 V 60 V CC – 64 V CC Tableau 29. Coupure tension haute 2.
FR 5. – UV Alarm – Alarme sonore tension basse Valeur par défaut : 10,5 V CC @ 12 V – 21 V CC @ 24 V – 42 V CC @ 48 V Modèle Plage de valeurs admissibles 12 V 10,5 V CC – 11,5 V CC 24 V 21 V CC – 23 V CC 48 V 42 V CC – 46 V CC Tableau 33. Alarme sonore tension basse Note La valeur du paramètre Alarme tension basse (UV Alarm) doit être égale ou supérieure à la valeur du paramètre Coupure tension basse (UVP) sinon l’appareil s’éteindra sans avoir émis d’alarme sonore. 6.
9. – Sync Frequency – Synchronisation de fréquence Valeur par défaut : 7 Hz En cas de dysfonctionnement du groupe électrogène. Le signal de sortie (fréquence trop basse) est utilisé en tant que source courant alternatif, la plage de fréquences de l’entrée CA peut être élargie. Exemple 1 : Entrée CA 230 V CA / 50 Hz – Valeur du paramètre : 7 Hz Lorsque la fréquence de sortie de l’onduleur SD est comprise entre 43 Hz et 57 Hz, le relais de transfert ferme le circuit.
FR 12. – Saving Level – Seuil de basculement en mode économie d’énergie Valeur par défaut : 0 Plage de valeurs admissibles : 3 – 7 Paramètre É tat 0 Défaut 10B 3 4% 13B 4 5% 14B 5 6% 15B 6 7% 16B 7 8% 17B Tableau 39. Seuil de basculement en mode éco 13. – Saving Interval – Temporisation mode économie d’énergie Valeur par défaut : 2,0 secondes Plage de valeurs admissibles : 1.0 s – 2.
Schéma 36.
FR 17. – Buzzer Setting – Paramétrage de l’alarme sonore Valeur par défaut : MSG, Alert, SHDN Message, alarme sonore, extinction Plage de valeurs admissibles : 0 – 7 Paramètre Buzzer Setting SETT Buzzer 0 Désactivé 1 SHDN 2 Alert 3 Alert, SHDN 4 MSG 5 MSG, SHDN 6 MSG, Alert 7 MSG, Alert, SHDN Tableau 44. Paramétrage de l’alarme sonore 18. – Alert Setting – Paramétrage du relais En situation d’alarme, le relais interne à contact sec se ferme / s’ouvre.
7. Recherche de pannes Problème Cause possible Solution Pas de courant en sortie - Cet état allume le voyant en rouge A. Clignotement rapide B. Clignotement lent Surtension en entrée (OVP) Vérifier la tension d’entrée et la réduire Sous-tension en entrée Recharger la batterie. (UVP) Vérifier les connexions et le câble Coupure de surchauffe (OTP) Améliorer la ventilation. S’assurer que les grilles d’aération de C. Clignotement intermittent l’onduleur ne sont pas obstruées.
No. 33, Sec. 2, Renhe Rd., Daxi Dist., Taoyuan City 33548, Taiwan Phone:+886-3-3891999 FAX:+886-3-3802333 http:// www.cotek.com.tw 2021.