Installation Guide

14
2-3-6. SP-4000 Specification
Electrical
Specification Model No.
Item S
P
-4
0
0
0
-124 S
P
-400
0
-14
8
Input
Characteristics
Voltage 24VDC 48VDC
Input Over-Voltage
Protection
M
33 ± 0.5VDC 66 ± 1.0VDC
Input Under-Voltage Protection 21 ± 0.5VDC 42 ± 1.0VDC
Voltage Range 21~33 VDC 42~66 VDC
No Load Current 2.0A @24VDC 1.0A @48VDC
Power Saving Mode <0.2A @24VDC <0.1A @48VDC
Output
Characteristics
Continuous Output Power 4000 VA 3%)
Maximum output Power (1Min) > 4000 VA~4600 VA (100%~115%)
Surge Power (1Sec) < 8000 VA
Frequency 50 / 60 Hz ± 0.5% (Dip Switch Selectable)
Output Voltage
100 / 110 / 115 / 120 VAC (± 5%)
(Dip Switch Selectable)
Efficiency max. 91% 91%
Short-Circuit Protection 1 Sec Shutdown
Output Waveform Pure Sine Wave (THD < 5%@ Normal Load)
N
Signal and Control
Remote Controller Panel Unit CR-8 / CR-16 (optional)
LED Indicator Red / Orange / Green LED
Dry Contact Terminal By a relay
Remote Control Terminal 6-port Green terminal (for inverter ON / OFF)
Protection
Input Protection
Over / Under Voltage, Reverse Polarity
(Internal Fuse)
AC Output Protection Short-Circuit, Overload
Others
Over / Under Temperature Protection
(by Heat sink Temperature +80
/-20 )
Environment
Operating Temp. -20
~40
O
Storage Temp. -30 ~70
Storage Temp. & Humidity 10 ~95% RH
Safety & EMC
Safety Standards Certified UL 458 ----
EMC standards Certified FCC class A
E-mark ----
Dimension(WxHxD) 255mm X 158mm X 462mm
Weight 10 KG
Cooling Temperature & Load Controlled cooling Fan
AC Transfer Function Accessories TR-40 (optional)
Table 11. SP-4000 for Output 100/110/115/120 VAC Specification.
Note
M Voltage range Please refer to Figure 3
N Normal load Condition
Vin =12.5V/25V/50V, Vo=100/110/115/120 VAC 80% Full load
(PF=1.0)
O Operating temperature
Please refer to Figure 4
P Warning
This is a class A product. In a domestic environment this product may cause radio
interference in which case the user may be required to take adequate measures.