SP1000 Manual

11
Electrical
Specification Model No.
Item S
P
-2
0
0
0
-212 S
P
-2
0
0
0
-224 S
P
-2
0
0
0
-24
8
Input
Characteristics
Voltage 12VDC 24VDC 48VDC
Input Over-Voltage
Protection
M
16.5 ± 0.3VDC 33 ± 0.5VDC 66 ± 1.0VDC
Input Under-Voltage
Protection
10.5 ± 0.3VDC 21 ± 0.5VDC 42 ± 1.0VDC
Voltage Range 10.5~16.5 VDC 21~33 VDC 42~66 VDC
No Load Current 1.8A @12VDC 1.0A @24VDC 0.5A @48VDC
Power Saving Mode <0.1A @12VDC <0.05A @24VDC <0.05A @48VDC
Output
Characteristics
Continuous Output
Power
2000 VA 3%)
Maximum output
Power (1Min)
> 2000 VA~2300 VA (100%~115%)
Surge Power (1Sec) < 3500 VA
Frequency 50 / 60 Hz ± 0.5% (Dip Switch Selectable)
Output Voltage
200 / 220 / 230 / 240 VAC (± 3%)
(Dip Switch Selectable)
Efficiency max. 94% 94% 95%
Short-Circuit
Protection
1 Sec Shutdown
Output Waveform
Pure Sine Wave (THD < 3%@ Normal Load)
N
Signal and Control
Remote Controller
Panel Unit
CR-8 / CR-16 (optional)
LED Indicator Red / Orange / Green LED
Dry Contact Terminal By a relay
Remote Control
Terminal
6-port Green terminal (for inverter ON / OFF)
Protection
Input Protection Over / Under Voltage, Reverse Polarity (Internal Fuse)
AC Output Protection Short-Circuit, Overload
Others
Over / Under Temperature Protection
(by Heat sink Temperature +80
/-20 )
Environment
Operating Temp.
-20
~40
O
Storage Temp. -30 ~70
Storage Temp. &
Humidity
10 ~95% RH
Safety & EMC
Safety Standards Certified EN 60950-1
EMC standards
Certified EN 55022 class A
; EN 55024; EN 61000-3-2, -3-3
EN 61000-4-2, 3, 4, 5, 6, 8, 11
E-mark Certified CISPR 25; ISO 7637-2
Dimension(WxHxD) 248mm X 83mm X 443mm
Weight 5.24 KG
Cooling Temperature & Load Controlled cooling Fan
AC Transfer Function Accessories TR-40 (optional)
Table 8. SP-2000 for Output 200/220/230/240 VAC Specification.
Note
M Voltage range Please refer to Figure 1
N Normal load Condition
Vin =12.5V/25V/50V, Vo=200/220/230/240 VAC 80% Full load (PF=1.0)
O Operating temperature
Please refer to Figure 2
P Warning
This is a class A product. In a domestic environment this product may cause radio
interference in which case the user may be required to take adequate measures.