Installation Manual

9
( will also require Fuse Block 4164) or equivalent.
The following sizes of cables and fuses are recommended for up to 6 ft. distance
between the batteries and the inverter. (Applies to both 120 VAC and 230 VAC
versions)
Model No. Wire AWG Inline Fuse
A 084 #422 / 421-T0001RS/0001RS
A 046 #842 / 841-T0001RS/0001RS
Connect DC input terminals to 24V / 48V battery or other DC power source.
[ + ] is positive, [ - ] is negative. Reverse polarity connection can blow the
internal fuse and may damage the inverter permanently.
WARNING!
Make sure that all the DC connections are tight (torque to 9 – 10 ft-lbs,
11.7 – 13 Nm). Loose connections could result in overheating and can be
a potential hazard.
WARNING!
The recommended inline fuse should be installed as close to the battery
positive terminal as pos
sible Failure to use a fuse on the “+” cable running
between the inverter and battery may cause damage to the cable /
inverter and will void warranty.
Also, only use high quality copper wire and keep the cable length short which is a
maximum of 3 - 6 feet.
M8 SCREW
PVC WIRE
(AWG#4 - #6)
POSITIVE +
RING
TERMINAL
PVC WIRE
(AWG#4 - #6)
RING
TERMINAL
NEGATIVE -