Installation Manual

13
z Connect AC input wiring to the inverter socket.
Please use the following information as your reference.
SR1000 Version
Socket
Wire color
Wire length / gauge
120 VAC 230 VAC
AC Output
Line (L)
NEMA I.E.C C13
Within 16 feet / AWG # 14~16
26~32 feet / AWG # 12~14
Neutral (N)
AC Input
Line (L)
I.E.C C14
Neutral (N)
Chassis Ground Green / Yellow or Bare copper
Note Please double check and review all the connections to ensure that the wires
are connected to the correct inlet.
SR1000T Version
Socket
Wire color
Wire length / gauge
120 VAC 230 VAC
AC Output
Line (L) Black Brown
Within 16 feet / AWG # 14~16
26~32 feet / AWG # 12~14
Neutral (N) White Blue
AC Input
Line (L) Black Brown
Neutral (N) White Blue
Chassis Ground Green / Yellow or Bare copper
Note Please double check and review all the connections to ensure that the wires
are connected to the correct terminals and that the connections are tight.
3-1-7. AC input breaker
The AC input circuit breaker protects the unit from overload. When an overload
condition occurs, the circuit breaker trips and disconnects the AC grid power input.
To reset it, push the circuit breaker button. The cause of tripping should be
ascertained and corrected before the unit is reset .