Installation Manual
15
4. Operation
4-1. Connecting the input power
Before making the DC input side connections, the main switch must be “OFF”.
4-2. Connecting the loads
z Calculate the total power consumption(W) of the output load. Make sure that the
total power consumption does not exceed the rated load.
z Should the total load exceed the rated capacity of the inverter, remove the
non-critical loads until the rated total has been reached.
4-3. Inverter Operation
z Set the power switch to the “ON” position. The buzzer will sound “beep beep”. The
inverter will carry out self-diagnosis and the LED will also appear various colors.
At the same time the LCD will display ”SR-1000 INVERTER INITIALIATION.”.
Finally, the buzzer will sound another “beep” and the “INVERTER” and status LED
will turn “Green”. The LCD Display will display “Vi, Vo, FQ, Io“.
The inverter will start operating normally.
z Set the power switch to the “OFF” position. THE, inverter stops and all the lights
that are on will, go off.
4-4. Protections Features
Model
DC Input (VDC) Over Temperature Protection
Over Voltage Under
Voltage
Alarm
Under Voltage INTERIOR HEAT SINK
Shut-down Restart Shut-down Restart Shut-down Restart Shut-down Restart
24V 30.1~34.1 28~32 19~23 18.1~22.1 23~27
65
45 105 75
48V 60.1 56~60 38~46 36.1~44.1 46~54