Installation Manual
18
5-3. Setup Menu – Operation and Instructions
Entering Setup Menu
consisting of three layers
(1)Select Menu Heading (2)Select Menu Item (3)Setting Value
5-3-1. User interface (Select Menu)
0). LCD Contrast Sets LCD screen contrast.
Default=50%
Setting Range= 0%~100%
1). LCD Auto-off
Sets LCD auto off timer.
Default=120 seconds.
Setting Range= Disable~250 seconds.
2). RS-232 Baud-rate
Sets standard RS-232 Baud-rate.
Default=4800
Setting Range= 1200/2400/4800/9600
3). Buzzer Setting
Sets the internal buzzer sound ON/OFF.
When setting, the LCD screen display, Buzzer “ON”, Buzzer “OFF”.
Default=MSG, Alert, SHDN
Setting Range= Disable / Shutdown / Alert / Alert, SHDN / Message / Message,
SHDN / Message, Alert / MSG, Alert, SHDN
Vi =XX.X Vo=XXX
FQ=XX.X Io =X.X
Main Menu:
Select
Menu:
User interface
Select Menu:
I/P Parameter
Select Menu:
O/P Parameter
Select Menu:
RST to default
Select Menu:
Select Item:
LCD Contrast
Select
Item:
Select Item:
LCD Auto-off
Select Item
:
RS232 Baudrate
Select Item:
Buzzer Setting
Select Item:
Alert Setting
0 1 2 3 4 6 7 8 9 10 11 12 13 14 15
Function
Code:
OVP Setting
Select Item:
OVP Recovery
Select Item:
UVP Setting
Select Item:
UVP Recovery
Select Item:
UV Alarm
Select Item
:
O/P Voltage
Select Item:
O/P Frequency
Select Item:
Sync Frequency
Select Item
:
Bypass relay
Select Item:
Overload Alarm
Select Item:
50%
LCD Contrast:
Setting
Value:
LCD Auto-off:
120S
RS232 Baudrate:
4800
Buzzer Setting:
MSG , Alert , SHDN
Alert Setting:
Alert , SHDN
OVP Setting:
32.00V
30.00V
OVP Recovery:
20.00V
UVP Setting:
25.00V
UVP Recovery:
21.00V
UV Alarm:
O/P Voltage:
230V
O/P Frequency:
50.00Hz
Sync Frequency:
7.00Hz
Bypass relay:
On-line
Overload Alarm:
100%
Press Button longer than 2 seconds. The inverter, enters the Setup Menus