Installation Manual

Lumi n S ma r t Pan el - Ou tdo or
DOCUMENTATION AND INSTALLATION MANUAL
9
STEP 2. Knock Out or Punch One Hole for 2” Conduit Fitting
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE.
AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES
CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
Tools: Screwdriver, pliers, drill (optional), and knockout punch (optional)
NOTE: Knockout hole location in electrical panel may vary depending on spacing constraints. Choose a
location that avoids existing obstructions and provides adequate clearance for routing of the LSP wire
whips. Use of existing pre-stamped 2” knockouts are acceptable provided there is sufficient clearance.
Otherwise, a 2” knockout punch (2-3/8hole) will be required to attach the LSP conduit. Additional
conduit fittings may be required depending on routing conditions, including installations that utilize
the bottom face of the electrical panel. Ensure the knockout hole location allows vertical mounting
of the LSP as shown in the following steps.