Installation Manual

Lumi n S ma r t Pan el - Ou tdo or
DOCUMENTATION AND INSTALLATION MANUAL
19
STEP 12. Connect One LSP Wire Labeled “Line 1 Breaker” to Circuit Breaker
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE.
AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES
CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
Tools: Screwdriver and wire stripper
NOTE: All LSP wires labeled “Line # Breaker” must connect to a breaker or be safely terminated with a
wire connector/cap. Lines 1-6 (6 AWG wire) can connect to circuit breakers rated up to 60 amps and
lines 7-12 (10 AWG wire) can connect to circuit breakers rated up to 30 amps (see pg. 35).
Line 1 Breaker
Load
Wire