Installation Manual

22
STEP 15. Repeat Steps 11-14 Until All LSP Line # Wires Are Connected
WARNING: HIGH VOLTAGE.
AVERTISSEMENT: HAUTE TENSION.
Tools: Screwdriver, wire stripper, and wire splice connectors
NOTE: All LSP wires labeled “Breaker” must connect to a breaker. Lines 1-6 (6 AWG wire) can connect to
circuit breakers rated up to 60 amps and lines 7-12 (10 AWG wire) can connect to circuit breakers rated
up to 30 amps (see pg. 35).
NOTE: The LSP can connect to up to 12 single-pole (or six double-pole) circuit breakers. Each hot leg of
a double-pole circuit must be connected to its own numbered Lumin wire set (ex. LSP controls a
clothes dryer. Dryer Leg "A" is connected to LSP Line 3. Dryer Leg "B" is connected to LSP Line 4).
NOTE: Controlling the circuit that powers the Internet/LAN equipment is not recommended,
manual control of the LSP will be lost when this circuit is switched off.
x 12
Line #
Load
Line # Breaker