Full Product Manual
1018454-EPage 26
STEP1. Cut hole within stud space behind heater in the back wall 8-1/4” high by 12-5/8” wide. The lower edge of the
hole to be 45-3/4” above the floor plate or 47” from the floor (with standard 2”x4” floor base) as shown in
Figure12-A(below).
STEP2. Install plaster ground frame for rear register in hole and nail frame to stud as shown in Figure12-B(below).
STEP3. REAR REGISTER INSTALLATION: Cut and remove embossed plates in inner and outer casing. Follow
instructions for installation of regular furnace.
STEP4. After furnace is installed, attach rear register grille as shown in Figures 13-B & 13-C (on page 27) by insertion
over plaster ground and attach with sheet metal screws, provided.
STEP5. Damper as shown in Figure 13-C (on page 27) can be adjusted from full open for maximum heat to
fully closed.
40542-A REAR REGISTER KIT(OptionalAccessory)
Installation Instructions for Gravity Vented Wall Furnaces
FIG. 12-A
ROUGH-IN DIMENSIONS FOR
REAR REGISTER
STUD
PLASTER
STUD
PLASTER
HOLE
FOR BACK
REGISTER
OPENING
7/8” FROM
EACH STUD
PLASTER
14-3/8”
8 ¼”
12 ⅝”
45-3/4”
PLATE
FIG. 12-B
PLACING FRAME FOR
REAR REGISTER
PLASTER
NAIL
TO STUD
STUD
PLASTER
PLATE
PLASTER
STUD
FIG. 12-C
40542-A REAR REGISTER KIT - W25/35 Series (Used on Single Wall Models Only)
Part Description Ref.No. Part No.
Damper 69 40375
Damper Spring 70 40377
Frame Assembly 71 40365
Register Chain 72 40379
Bell, Pull 73 85003
Register Assembly 74 40355
Installation Instructions - - 84504
74
71
73
72
69
70