OIL-LESS REFRIGERANT RECOVERY SYSTEM MODEL CR500 SERIES TO BE OPERATED BY QUALIFIED PERSONNEL ONLY! This equipment has been certified by Underwriter Laboratories (UL) to meet or exceed EPA regulations per ARI 740-95 for refrigerants 12, 134a, 22, 500 and 502.
TABLE OF CONTENTS INTRODUCTION .............................................................. 2 GENERAL SAFETY INSTRUCTIONS ............................... 3 SPECIFICATIONS ............................................................ 4 DIRECT LIQUID OR VAPOR RECOVERY ........................ 5 LIQUID PUSH-PULL RECOVERY .................................... 5 ROUTINE MAINTENANCE ............................................... 6 TROUBLE SHOOTING CHART........................................ 7 HELPFUL HINTS ...
UNIT CONSISTS OF: •PRO-SET® model CR500 • Power Cord Set (110 volt version only) • Operation Manual • Suction Gauge and Valve Discharge Gauge and Valve DISCHARGE Port SELF-CLEARING Valve SUCTION Port w/Filter POWER Switch Fan Thermal Circuit Breaker IEC 320 Electrical Inlet GENERAL SAFETY INSTRUCTIONS ONLY QUALIFIED SERVICE PERSONNEL SHOULD OPERATE THIS UNIT. MOST STATES, COUNTRIES, ETC… MAY REQUIRE THE USER TO BE LICENSED. PLEASE CHECK WITH YOUR LOCAL GOVERNMENT AGENCY.
Direct Vapor Direct Liquid Push-Pull Liquid Compressor Type Dimensions Weight Operating Temperature Range Power Source Power Consumption Suction Pressure Gauge Discharge Pressure Gauge Filtration Shut-off Valves Construction Overload Protection High Pressure Shut-off Refrigerants CR500J CR500S 1/3 HP Oil-less Reciprocating Compressor 20cm (8”) wide x 37cm (14.5”) long x 30.5cm (12”) high 9.1 kg (20 lbs.
DIRECT VAPOR OR LIQUID RECOVERY OPERATION 1. 2. 3. 4. 5. 6. 7. 8. CR UNIT Connect the unit as shown in Diagram 1. Open the vapor valve on the RecovVAPOR VALVE ery Tank. REFRIGERANT Open DISCHARGE valve on CR CONTAINING UNIT TO BE unit. SERVICED Rotate the center valve to the “RESERVICE PORT COVERY” position. RECOVERY TANK Turn power switch to “ON” position. SCALE Once unit has started, open the SUCTION valve on the CR unit to start the refrigerant flow.
ROUTINE MAINTENANCE FILTER MAINTENANCE - the CR SERIES is equipped with a 100 mesh screen filter. This filter should be checked periodically. A partially clogged filter will slow down the recovery rate of this unit. Replace the filter cartridge as follows: 1. Use a 7/8” socket or boxed end wrench to loosen the suction port as shown in Figure 1. 2. Once loose, remove the suction port- filter cartridge assembly is shown in Figure 2. 3. Either clean the current cartridge or replace with new cartridge. (Item NO.
TROUBLE SHOOTING CHART PROBLEM: The unit will only pull down to 0 pressure or a slight vacuum. SOLUTION: Remove refrigerant hose from Suction port. Place a cap on this port: 1. If the unit pulls a vacuum, then the low side leak is somewhere between the refrigerant hose and the equipment being recovered. 2. If the unit does not pull a vacuum, then suspect an internal low side leak on the CR unit. PROBLEM: The unit starts for a few minutes, then shuts-off. SOLUTION: The high pressure switch has activated.
WARRANTY & REPAIR POLICY CPS® Products, INC. guarantees that all products are free of manufacturing and material defects for one year. If the equipment should fail during the guarantee period it will be repaired or replaced (at our option) at no charge. This guarantee does not apply to equipment that have been altered, misused, or returned solely in need of field service maintenance. This repair policy does not include equipment that is determined to be beyond economical repair.