Technical data

62
GridV.Unbal(%)
Threshold value of grid
voltage unbalance
{0.1, 2.6, 10.0}
(2) ”3 ON/OFF” menu: Set up the start-up and shut-down control parameters.
Table 5-4 Start-up and turn-off control parameters
Parameter name
Description
Setup range (lower limit,
default & upper limit)
PVStartVol(V)
PV start-up voltage
{300.0, 330.0, 400.0}
SoftStep(KW/S)
Soft step
{0.01, 1.00, 2.00}
SoftOffOption
Soft turn off option
{Ban, Ban, Enable}
OffPStep(KW/S)
Turn off power step
{0.01, 1.50, 2.00}
IsoResis(KOhm)
Isolation resistance
{10.0, 200.0, 1000.0}
GridReStep(KW/S)
Grid fault recovery step
{0.01, 0.04, 2.00}
(3) ”4 PowerContr” menu: relative functions of active, reactive power control
and over-frequency derating, including “ActiveContr(%)”, “RePowerContr”
and ”FreqDeratCtrl” menus.
1. “ActiveContr(%)” menu: adjust the active power of AC output, the
range is 0~100.0%.
2. “RePowerContr” menu: set up the reactive power control mode,
including 6 submenus: “1. None”, “2. Dispatch”, “3. Q Set”, “4. PF Set”, “5.
PF(P) Set” and “6. Q(U) Set”.
1 None
2 Dispatch
3 QReactSet
4 PF Set
5 PF(P) Curve
6 Q(U) Curve
Figure 5-16 Reactive power mode