Technical data

63
1). None No mode/disable reactive power mode
2). Dispatch Remote power dispatch mode
Note: The ActivePower, PF and Q value can be adjusted by remote software if
the “Dispatch” is selected.
3). QReactSet Set the Q value
Note: Change the reactive power by adjusting the Q value (reactive
compensation)
4). PF Set Set the PF value
Note: Change the reactive power by adjusting the PowerFactor
5). PF(P) CurvePF curve mode
Note: The power factor changes according to the power change, as shown in
Figure 5-17:
Figure 5-17 PF(P) curve mode
6). Q(U) CurveQ(U) curve mode
Capacitive
PF
-1
1
Inductive
(PFCurveP1,PFCurvePF1)
(PFCurveP2,PFCurvePF2)
(P%)
INSTRUCTION:
The PF (P) Curve function is only available for VDE-4105, CEI 0-21
and IEEE-1547 grid standards.