Owner`s manual

ELECTRICAL
Wiring Connections
[*_.WARNING ] Fire hazard. Incorrect voltage can cause
a fire or seriously damage the motor and voids the war-
ranty. The supply voltage must be within _+10% of the
motor nameplate voltage.
NOTICE: Dual-voltage motors are factory wired for
230 volts. If necessary, reconnect the motor for 115
volts, as shown. Do not alter the wiring in single volt-
age motors.
Install, ground, wire, and maintain your pump in com-
pliance with the National Electrical Code (NEC) or the
Canadian Electrical Code (CEC), as applicable, and
with all local codes and ordinances that apply. Consult
your local building inspector for code information.
Motor wires connect here.
-Power supply wires connect here.
230 Volt: Connect 2 hot wires (black and red)
here and cap the white (neutral) wire. it does
not matter which wire goes to which screw.
115 Volt: Connect one hot wire (black or red)
to one of these screws (it doesn't matter
which one). Connect the white (neutral) wire
to the other screw. Cap any remaining
black or red wires.
prevent strain
on the terminal screws.
Connect the green (or bare copper) ground wire
to the green ground screw. 31870398
Figure I0 - Pressure switch wiring
Connection Procedure
1.
2.
.
.
Connect the ground vdre first as shown in Figure 10.
The ground wire must be a soEd copper wire at least
as large as the power supply wires.
There must be a solid metal connection between the
pressure switch and the motor for motor grounding
protection. If the pressure switch is not connected
to the motor, connect the green ground screw in the
switch to the green ground screw under the motor
end cover. Use a solid copper vdre at least as large
as the power supply wires.
Connect the ground wire to a grounded lead in a ser-
vice panel, to a metal undergrotmd water pipe, to a
metal well casing at least ten feet (3/7I) long, or to a
ground electrode provided by the power company
or the hydro authority.
Connect the power supply wires to the pressure
switch as shown in Figure 10.
Pump
Model
390.2519
390.2522
RECOMMENDED FUSING AND WIRING DATA
Motor
Horse-
power
3/4
Volts
115
23O
115
230
Max.
Load
Amperes
12.4
6,2
14,2
7.6
Branch*
Delayed
Fuse
Rating
Amps
20.0
15.0
20.0
15.0
Distancein Feet From
Motorto Meter
0 51 101 201
to to to to
50 100 200 300
Win_Size
12 12 10 8
14 14 14 14
12 12 8 6
14 14 14 14
* Time delayed fuses are recommended instead of fuses in any motor circuit.
10