DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL Notice The information in this document is subject to change without notice. PAT makes no warranty of any kind with regard to this material, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. PAT shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance or use of this manual.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL TABLE OF CONTENTS Section 1 2 3 4 5 6 7 8 9.1 9.2 9.3 9.4 10.1 10.2 11.1 11.2 12 13 14 15 16 17 18.1 18.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 1 1. General Information The DS 350 load moment indicator (LMI) with boom control extension is designed to aid the crane operator through the crane operations. The DS 350 with boom control extension is not, and shall not, be a substitute for good operator judgment, experience and use of accepted safe crane operating procedure. 2.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 2 4. Service and Maintenance Daily maintenance of the load moment indicator consists of inspecting: 1. The electrical wiring connecting the various parts of the system. If electrical wiring is damaged, it shall be replaced immediately. 2. If the insulation is worn on the length sensor cable or cable guides are damaged, these parts shall be replaced. 3. Check the anti two-block limit switches for freedom of movement. 4.
LMI Circuit Boom control circuit 031-300-190-039 Rev. B 4/30/99 Prop. * = RT 865BXL only OM 2- way valve CM 2- way valve Proportional output / extend Proportional output / retract Tele out of sequence Rod side dump valve IM 2- way valve Area def.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 4 Auto mode / Manual mode: The operator selects auto mode or manual mode using the rocker switch in the dash board. Auto mode is the working mode and manual mode is used for rigging or sequencing purpose only. Pilot pressure switch signal / Analog output signal: Two pressure switches in the pilot pressure circuit are used to distinguish between boom extend or boom retract.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 5 Length sensors: Three length sensors are mounted to the boom base section to measure the overall length, the inner mid section length and the center mid section length. The software utilizes the signals to calculate the outer mid and fly section length. Disengage the boom stop to retract the boom completely. With retracted main boom the overall boom length signal is -500 mV (A101-X1/10).
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 6 Center mid retract and % reset switch: The proximity switch on the inner mid section provides a (+24V) signal to central unit terminal A 114 X1/9 when the center mid section is fully retracted. The signal resets the center mid percentage to 0%. Refer to Parts & Installation Manual and follow the installation instructions for switch and target adjustment.
7 DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL Output for two- way valves: A pair of two- way valves controls the oil to each tele- cylinder. The relay output K2, K6, K7 operates the pair of two- way valves in automode. The valve need to be de-energized to operate the particular cylinder. The valves for the sections that are not selected are powered to prevent movement of the other cylinders.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 8 Rod side dump valve: Relay K3 controls the rod side dump valve. The valve dumps the rod side pressure when the controller is in neutral position and during the time the section stops while changing over to another section. Controller Extend on Retract on Neutral Retracted/ retract on 031-300-190-039 Rev.
9 DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 6. Boom Sequence Main Boom: Mode Auto B Auto B Auto B Auto B Auto B Auto B Auto B Auto B IM % 0 50 50 75 75 100 100 100 CM % 0 0 50 50 75 75 100 100 OM % 0 0 0 0 0 0 0 100 FLY % 0 0 0 0 0 0 0 100 Mode Auto A * Auto A * Auto A * Auto A * IM % 0 0 0 100 CM % 0 100 100 100 OM % 0 0 100 100 FLY % 0 0 100 100 OM % 0 0 0 100 FLY % 0 0 0 100 *= Mode A not available on RT 865 BXL Extensions: Mode Auto Auto Auto Auto 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 7. Boom Control Flow Operator moves controller to extend or retract position. Directional pressure switch transmits signal to B.C.S. B.C.S. checks input for Automode. off Operation in manual mode. on B.C.S. checks input for A mode or B mode. B.C.S. checks the retract and % reset switch and boom length. Refer to section 6 for sequencing information. continue on next page Drawing 2a. 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL Continuation The B.C.S. relays K2, K6, K7 provide power to the 2 way valves allowing oil flow to the selected cylinder. The B.C.S. relay K3 controls the rod side dump valve. Refer to section 5. The B.C.S. analog output signal opens the pressure reducing valves (proportional valves). While estending and retracting the B.C.S. monitors each section length. incorrect correct The B.C.S. controls the speed and sequence of each boom section.
12 DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 8. Ramping Ramp Value Max. Ramp Value Ramp down Max. Ramp Value Ramp up Boom Section A -e.g. IM- Min. Ramp Value Change Over Drawing 3. Boom Section B -e.g. CM- Boom Length Ramp value: A hex value in the software which determines the output current to the proportional valve. Max. ramp value: The maximum hex value (hex 255) equals to 800 mA valve (pressure reducing valve).
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 13 9.1 DS 350 G - Boom Components and Setup 4 Inner mid length sensor LG 221 8/9 Inner mid % reset switch Center mid length and angle sensor LWG 221 3 7 4 7 Center mid retract and % reset switch 5 1 2 Inner mid retract switch Overall boom length sensor LG 208 Outer mid retract and % reset switch Drawing 4. 1. Pre-tension the cable reel spring by rotating drum (16) revolution counterclockwise.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 14 1. Place tie wrap, 120 degree apart around the bushing. Wrap cable (8-10) revolutions over the tie wraps starting from the outside and working inward. Allow ample cable to reach the junction box. Secure with (2) additional tie wraps. See page 17. 2. Check proximity switch installation (0.44 inch from target) when boom sections are fully retracted. 3. This target is only installed if the boom is equipped with a boom extension stop block. 4.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 15 9.2 Length Transducer Adjustment Drawing 6. PAT Equipment Corporation reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential and are not to be used or reproduced without the written consent of PAT Equipment Corporation. This drawing is subject to technical modification without prior notice. 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 16 9.3 DS 350 G Superstructure Components - TMS/TTS 870 Drawing 7. PAT Equipment Corporation reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential and are not to be used or reproduced without the written consent of PAT Equipment Corporation. This drawing is subject to technical modification without prior notice. 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 17 9.4 DS 350 G Superstructure Components - RT 865 BXL Drawing 8. PAT Equipment Corporation reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential and are not to be used or reproduced without the written consent of PAT Equipment Corporation. This drawing is subject to technical modification without prior notice. 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 18 10.1 DS 350 G LMI central unit (751) - TMS/TTS 870 & RT 865 BXL Diode extension board Real time clock (Timer board) with e-prom sockets Diode extension board Analog output extension board 3rd wrap warning relay board Digital input extension board Decoder board Key to open central unit enclosure Termial board Drawing 9. PAT Equipment Corporation reserves proprietary rights to this drawing and to the data shown there on.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 19 10.2 LMI Terminal board - TMS 870, TTS 870 and RT 865 BXL X1 X1 X1 F8 F7 F6 K6 F5 K7 K5 F4 X1 F3 K3 F2 K4 K2 X1 K1 K9 F1 K8 K10 X1 X1 X1 X1 Drawing 10. PAT Equipment Corporation reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential and are not to be used or reproduced without the written consent of PAT Equipment Corporation.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 20 11.1 Wiring Schematic - TMS 870/ TTS 870 Drawing 11.1 PAT Equipment Corporation reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential and are not to be used or reproduced without the written consent of PAT Equipment Corporation. This drawing is subject to technical modification without prior notice. 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 21 11.1 Wiring Schematic - TMS 870/ TTS 870 Drawing 11.2 PAT Equipment Corporation reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential and are not to be used or reproduced without the written consent of PAT Equipment Corporation. This drawing is subject to technical modification without prior notice. 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 22 11.1 Wiring Schematic - TMS 870/ TTS 870 Drawing 11.3 PAT Equipment Corporation reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential and are not to be used or reproduced without the written consent of PAT Equipment Corporation. This drawing is subject to technical modification without prior notice. 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 23 11.1 Wiring Schematic - TMS 870/ TTS 870 Drawing 11.4 PAT Equipment Corporation reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential and are not to be used or reproduced without the written consent of PAT Equipment Corporation. This drawing is subject to technical modification without prior notice. 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 24 11.1 Wiring Schematic - TMS 870/ TTS 870 Drawing 11.5 PAT Equipment Corporation reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential and are not to be used or reproduced without the written consent of PAT Equipment Corporation. This drawing is subject to technical modification without prior notice. 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 25 11.2 Wiring Schematic - RT 865 BXL Drawing 12.1 PAT Equipment Corporation reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential and are not to be used or reproduced without the written consent of PAT Equipment Corporation. This drawing is subject to technical modification without prior notice. 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 26 11.2 Wiring Schematic - RT 865 BXL Drawing 12.2 PAT Equipment Corporation reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential and are not to be used or reproduced without the written consent of PAT Equipment Corporation. This drawing is subject to technical modification without prior notice. 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 27 11.2 Wiring Schematic - RT 865 BXL Drawing 12.3 PAT Equipment Corporation reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential and are not to be used or reproduced without the written consent of PAT Equipment Corporation. This drawing is subject to technical modification without prior notice. 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 28 11.2 Wiring Schematic - RT 865 BXL Optional Data Logger Connection Drawing 12.4 PAT Equipment Corporation reserves proprietary rights to this drawing and to the data shown there on. The drawing and data are confidential and are not to be used or reproduced without the written consent of PAT Equipment Corporation. This drawing is subject to technical modification without prior notice. 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 12. Boom Length Percentage Error Boom length percentage error Keep the boom stop block latched. Switch to Manual Mode and retract the boom completely. Is the percentage reading (1%, 0%, 0%)? Yes No The LMI does not recognize the one or more reset switch signals. Check proximity switch target adjustment as per section 9.1. If damage is visible install new switch.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 12. Continuation Continuation Is the voltage correct? No Yes Keep the inner mid section retracted. Measure the inner mid reset switch signal at terminal 3 (24V) and 5 (GND) in the junction box at the front of the boom base section. Refer to section 9.1 and 11. Is the voltage correct ? Faulty voltage supply wiring to switch.Refer to section 11. Replace defective cables.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 12. Continuation Continuation Is the voltage correct? No Yes Measure the IM reset switch signal at terminal 15 (24V) and 14 (GND) in the boom base junction box. Refer to section 9.1 and 11. Is the voltage correct? Faulty wiring in cable connecting the junction box with the length sensor. Refer to section 11 to locate the fault. No Yes Measure the IM reset switch signal at central unit terminal A104 80 (24V) and A 101 36 (GND).
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 12. Continuation Continuation Is the voltage correct? No Yes Measure the CM reset switch signal at terminal 10 (24V) and 9 (GND) in the length sensor LG221. Refer to section 9.1 and 11. Is the voltage correct ? Defective CM reset switch. Replace proximity switch. No Yes Measure the CM reset switch signal at terminal 30 (24V) and 14 (GND) in the boom base junction box. Refer to section 9.1 and 11.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 12. Continuation Continuation Is the voltage correct? No Yes Faulty wiring in cable connecting the boom base junction box with the LG221. Refer to section 11 to locate the fault. Measure the CM reset switch signal at central unit terminal A114 9 (24V) and A104 36 (GND). Refer to section 9.3, 10 and 11. Is the voltage correct? No Yes Measure voltage supply to OM switch at terminal 11 (+24V) and 9 (GND) in the center mid junction box.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 12. Continuation Continuation Is the voltage correct? No Yes Faulty wiring in cable connecting the central unit and the boom base junction box. Refer to section 11 to locate the fault. Measure voltage supply to CM switch at terminal 7 (+24V) and 5 (GND) in the inner mid junction box. Refer to section 9.1 and11. Is the voltage correct ? No Yes Keep the outer mid (OM) section retracted.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 12. Continuation Continuation Is the voltage correct? No Yes Faulty wiring in cable connecting the the center mid junction box and the LWG 221. Refer to section 11 to locate the fault. Measure the CM reset switch signal at terminal 10 (24V) and 9 (GND) in the length- angle sensor LWG221. Refer to section 9.1 and 11.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 12. Continuation Continuation Is the voltage correct? No Yes Faulty wiring in cable connecting the boom base junction box with the LWG 221. Refer to section 11 to locate the fault. Measure the OM reset switch signal at central unit terminal A104 78 (24V) and A104 36 (GND). Refer to section 9.3, 10 and 11. Is the voltage correct? No Yes Defective digital input 4, 5 on main board or digital input 5 on extension board.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 13. Main Boom Length Error Main boom length error In manual mode retract all boom sections. Pull the boom stop and retract the inner mid section completely. Is the main boom length indicated correctly? Yes No CAUTION: High tension on cable reel drum! CAUTION: To avoid length potentiometer damage, do not turn the length potentiometer past the stop.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 13. Continuation Continuation Has the adjustment corrected the boom length indication? Yes No Continue with B on page 40 Check the power supply to the length sensor. Measure the power supply voltage at central unit terminal A104 X1/11(-5V) and A104 X1/8(GND). Is the voltage correct (-5V)? No Yes Possible short or wiring fault between central unit and cable reel.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 13. Continuation Continuation Is the voltage correct (-5V)? No Yes Faulty wiring between central unit and length transducer. Check wiring, junction boxes and connectors for faulty wiring. Verify the length sensor signal. Measure the voltage at the length transducer (LG 208) terminal 1 (GND) and 2 (-500mV) with fully retracted boom. Is the voltage correct (-500mV)? No Yes Check the length signal in the central unit.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 13. Continuation Continuation Is the voltage correct (-500mV)? Yes No Check the wiring that connects the LG 208 with the central unit. Inspect the cable and connectors. Have you found any wiring faults? Main board component defective. Contact authorized service dealer for the board replacement procedure. Yes No Connect the voltmeter central unit terminal A104 X1/10 (signal) and A104 X1/8 (GND).
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 13. Continuation Continuation Is the voltage decreasing from -500mV to -4.5V ? Yes No Check the wiring between length transducer LG 208 and central unit. Inspect cable connectors and junction boxes . Have you found any wiring faults? Main board component defective. Contact authorized service dealer for main board replacement procedure. Yes No Connect the voltmeter to terminal 2 (signal) and terminal 1 (GND) in the cable reel.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 13. Continuation Continuation Is the voltage correct? [O turns = - 500mV 10 turns= - 4.5V] Yes No Defective length potentiometer assembly. Replace and adjust length potentiometer. Refer to drawing on page 18. 031-300-190-039 Rev. B 4/30/99 Refer to page 18 and reset length transducer. Continue with section 14.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 14. Inner Mid Length Error Inner mid length error In manual mode retract all boom sections. Pull the boom stop and retract the inner mid section completely. Is the inner mid boom length indicated correctly? Yes Continue with B on page 46 No CAUTION: High tension on cable reel drum! CAUTION: To avoid length potentiometer damage, do not turn the length potentiometer past the stop.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 14. Continuation Continuation Has the adjustment corrected the inner mid length indication? Yes No Continue with B on page 46 Check the power supply to the length sensor. Measure the power supply voltage at central unit terminal A104 X1/11(-5V) and A104 X1/8(GND). Is the voltage correct (-5V)? No Yes Possible short or wiring fault between central unit and cable reel.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 14. Continuation Continuation Is the voltage correct (-5V)? No Yes Faulty wiring between central unit and length transducer. Check wiring, junction boxes and connectors for faulty wiring. Verify the length sensor signal. Measure the voltage at the length transducer (LG 221) terminal 1 (GND) and 2 (-500mV) with fully retracted boom. Is the voltage correct (-500mV)? No Yes Check the length signal in the central unit.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 14. Continuation Continuation Is the voltage correct (-500mV)? Yes No Check the wiring that connects the LG 221 with the central unit. Inspect the cable and the connections. Have you found any wiring faults? Main board component defective. Contact authorized service dealer for the board replacement procedure. Yes No Connect the voltmeter to central unit terminal A104 X1/24(signal) and A104 X1/8 (GND).
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 14. Continuation Continuation Is the voltage decreasing from -500mV to -4.5V ? Yes No Check the wiring between length transducer LG 221 and central unit. Inspect cable connectors and junction boxes . Have you found any wiring faults? Main board component defective. Contact authorized service dealer for main board replacement procedure. Yes No Connect the voltmeter to terminal 2 (signal) and terminal 1 (GND) in the cable reel.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 14. Continuation Continuation Is the voltage correct? [O turns = - 500mV 10 turns= - 4.5V] Yes No Defective length potentiometer assembly. Replace and adjust length potentiometer. Refer to drawing on page 18. 031-300-190-039 Rev. B 4/30/99 Refer to page18 and reset length transducer. Possible main board defect. Contact authorized service dealer for further assistance.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 15. Center Mid Length Error Center mid length error In manual mode retract all boom sections. Pull the boom stop and retract the inner mid section completely. Is the center mid length indicated correctly? Yes No Continue with B on page 52 CAUTION: High tension on cable reel drum! CAUTION: To avoid length potentiometer damage, do not turn the length potentiometer past the stop.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 15. Continuation Continuation Has the adjustment corrected the center mid length indication? Yes No Check the power supply to the length sensor. Measure the power supply voltage at central unit terminal A104 X1/11(-5V) and A104 X1/8(GND). Is the voltage correct (-5V)? Continue with B on page 52 No Yes Possible short or wiring fault between central unit and cable reel.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 15. Continuation Continuation Is the voltage correct (-5V)? No Yes Faulty wiring between central unit and length transducer. Check wiring, junction boxes and connectors for faulty wiring. Verify the length sensor signal. Measure the voltage at the length transducer (LWG 221) terminal 1 (GND) and 2 (-500mV) with fully retracted boom. Is the voltage correct (-500mV)? No Yes Check the length signal in the central unit.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 15. Continuation Continuation Is the voltage correct (-500mV)? Yes No Check the wiring that connects the LWG 221 with the central unit. Inspect the cable and the connections. Have you found any wiring faults? Main board component defective. Contact authorized service dealer for the board replacement procedure. Yes No Connect the voltmeter central unit terminal A104 X1/73 (signal) and A104 X1/8 (GND).
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 15. Continuation Continuation Is the voltage decreasing from -500mV to -4.5V ? Yes No Check the wiring between length transducer LWG 221 and central unit. Inspect cable connectors and junction boxes . Have you found any wiring failures? Main board component defective. Contact authorized service dealer for main board replacement procedure. Yes No Connect the voltmeter to terminal 2 (signal) and terminal 1 (GND) in the cable reel.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 15. Continuation Continuation Is the voltage correct? [O turns = - 500mV 10 turns= - 4.5V] Yes No Defective length potentiometer assembly. Replace and adjust length potentiometer. Refer to drawing on page 18. 031-300-190-039 Rev. B 4/30/99 Possible main board defect. Contact authorized service dealer for further assistance.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 16. No Extend or Retract Function in Automode Boom does not extend or retract in automode. Switch to manual mode and extend or retract the boom manually. Does the boom extend or retract? No Yes Switch to automode. Start the engine and operate the extend control. Measure the voltage at central unit terminal A104 X1/38 (24V) and A104X1/37 (GND) while operating the extend control.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 16. Continuation Continuation Switch to automode. Start the engine and operate the retract control. Measure the voltage at central unit terminal A104 X1/40 (24V) and A104 X1/39 (GND) while operating the extend control. Is the voltage correct? No Yes Select the service screen on the console by pressing the two outer keys to the left of the LCD simultaneously. The ramping value for the selected section shall increase from 0 to 255.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 17. Out of Sequence Warning Boom sections are out of sequence (Automode). Follow the instruction in section 12. Is the problem corrected? Yes No End Follow the instruction in section 13. Is the problem corrected? Yes No Continue on next page 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 17. Continuation Continuation Follow the instruction in section 14. Is the problem corrected? Yes No Follow the instruction in section 15. Is the problem corrected? End Yes No Continue on next page 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 17. Continuation Continuation With outer mid section completely retracted check the adjustment for the OM retract switch target. Refer to section 9.1. Is the switch and target adjusted correctly? No Yes Measure switch signal at central unit terminal A104 X1/ 76 (24V) and A104 X1/ 36 (GND). Is the voltage correct? Adjust OM retract switch and target. Yes No Continue on next page 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 17. Continuation Continuation Faulty wiring. Check the voltage at terminal 17 (24V) and 13 (GND) in boom base junction box. Refer to section 9.and 11. Have you located a wiring fault? Yes No Correct the wiring between boom base junction box and central unit. Refer to section 11. Measure switch signal at LWG 221 terminal 10 (24V) and 9 (GND). Is the voltage correct? Yes No Continue on next page 031-300-190-039 Rev.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 17. Continuation Continuation Check the signal at terminal 10 (24V) and 9 (GND) in CM junction box. Refer to section 9.1 and 11. Is the voltage correct? No Yes Retract all boom section in manual mode and let the system reset boom percentage. Recheck. End 031-300-190-039 Rev. B 4/30/99 Defective OM retract switch. Replace proximity switch. Refer to section 9. and 11.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 62 18.1 Additional Error Codes - Operational Error code Description Solution E18 Front Stabilizer overloaded Achieve a safe working area immediately. E83 The outer mid section and fly section are not fully retracted while the center mid section or the inner mid section retracts or extends. No cut off with E83, but flashing prewarning light in console and reduced capacity chart (rigging mode). Select manual mode.
DS 350 G Boom Control Troubleshooting- TMS/TTS870 / RT865 BXL 63 18.2 Additional Error Codes - System Error code Description Solution E 47 Processor can not locate analog output circuit for center mid section Analog output circuit defective. Replace module. Ribbon cable (DS 350G only) defective or bad connection. Replace cable. Decoder circuit defective. Replace decoder module(DS 350G only).