User's Manual

Table Of Contents
ADDICT v3.0.1 User Manual DALI Functionality
©2017 All rights reserved - 24 -
First
Second
Result
Device
Scene
Device
Scene
Address
0 15
Address
0 15
The selected scene in the first device is swapped with
the selected scene in the second device.
Address
ALL
Address
ALL
All scene levels in the first device are swapped with the
scenes in second device (scene 0 swapped with scene
0, scene 1 swapped with scene 1 etc.)
Group
0 15
Same as first
group
0 15
For each device in the selected group, the first selected
scene is swapped with the second selected scene.
If Live Preview is enabled:
Selecting an address/group will cause that address/group to be set at maximum and all
others at minimum.
Selecting a scene will cause that scene to be recalled for the associated device.
Selectable values:
First (next to “Swap”) device (A00-A63, G00-G15, ALL) The address or group of the
device(s) containing the first scene to be swapped.
First scene (0-15, ALL) The scene(s) to be swapped from the first device(s).
Second (next to “With”) device (A00-A63, G00-G15, ALL) The address or group of the
device(s) containing the second scene to be swapped.
Second scene (0-15, ALL) The scene(s) to be swapped from the second device(s).
Pressing enter will cause the swap function to be performed.
DALI Types
The Device Types menu provides a summary of the information from a device based on its
device type. For DALI devices that have more than 1 type, the settings from both of those types
can be displayed by selecting the appropriate type. The pages displayed for each type depends
on the type that is selected.
Summary
Summary displays a set of 9 information screens or pages for each address on the DALI line.
Primarily the information pages display the common stored settings, although the first page also
shows the current arc level and state of the lamp.
The following outlines what is included on each page:
Page 1 - Current arc power level, lamp status
Page 2 - Group Assignments
Page 3 - Stored levels for scenes 0-3
Page 4 - Stored levels for scenes 4-7
Page 5 - Stored levels for scenes 8-11
Page 6 - Stored levels for scenes 12-15
Page 7 - Stored minimum, maximum and power-on levels
Page 8 - Stored system failure level, fade time and fade rate
Page 9 - DALI compliance version, device type and physical minimum level (unchangeable)
Use the increase and decrease buttons to select the address, and use the up and down buttons
to scroll through the pages. Also, pressing enter will cause the displayed information to toggle
between actual values and alternative values (e.g. will toggle between showing actual levels and
percentages for level settings).