User's Manual

Table Of Contents
ADDICT v3.0.1 User Manual DALI Functionality
©2017 All rights reserved - 28 -
Recall Data
Store Data
Sniff to PC
Start Sniffing
The ADDICT
®
will start sniffing the DALI line until the user presses enter, or 250 packets are
received. Every 2 hours, if the 250-packet limit has not been reached, the time will reset to start
from 0 again. When a packet is detected during sniffing, its contents are displayed on the screen
(as well as the number of recorded packets).
The following show the screen before any packets have been detected, and the screen after 24
packets have been detected so far with the last packet being a “Maximum” command to the
device with address 4.
During sniffing, the ADDICT
®
will store the detected packet data in its volatile RAM memory. This
means that the data will be lost if the ADDICT
®
is turned off or the data will be overwritten if
sniffing is started again. To prevent this data from being lost or overwritten, the ADDICT
®
contains two sections in its eeprom (designated Alpha and Beta) that can each store a block of
250 packets and be later recalled after the ADDICT
®
has been turned off or sniffing was
restarted.
When sniffing has been stopped (by one of the conditions mentioned above), the ADDICT
®
displays the packets that were detected during sniffing. Since this is the same as what is
displayed under Recall Data, it will be described in that section.
Note: sniffing can also be stopped by pressing escape, but the ADDICT
®
will show the Sniffing
menu instead of the Recall Data screen. However, the packets that were detected before
escape was pressed can still be displayed by going to Recall Data.
Selectable values: none
Recall Data
Recall Data is a menu with four options:
Recall Last display the packets most recently sniffed
Recall Alpha display the packets that are stored in the Alpha eeprom memory location
Recall Beta display the packets that are stored in the Beta eeprom memory location
Send all to PC transmits all the stored packet data (in Last, Alpha and Beta) via the PC
communications link
After selecting one of the recall options, the packet display screen is shown.