Store Data
Store Data is a menu with two items:
Last to Alpha store the most recently sniffed packet data in the Alpha eeprom location
Last to Beta store the most recently sniffed packet data in the Beta eeprom location
After one of the Store Data menu options has been selected a confirmation screen is displayed
(unless there are no packets to be stored), since all data currently stored in that location will be
overwritten with the new packet data (even if the number of new packets is less than what was
currently stored).
After confirming, the stored packets can be viewed at any time (even after the ADDICT
®
has been
switched off) under the Recall Data menu.
Selectable values:
Confirmation (YES, NO) Press enter to confirm storing packet data to eeprom, YES to
store, NO to cancel
Sniff to PC
Sniff to PC is like the standard sniffing mode, except the detected packet data is transmitted via
a PC communications link to a PC (or other device capable of receiving RS-232 serial data)
instead of being recorded by the ADDICT
®
. This allows for an unlimited number of DALI packets
to be detected (instead of a maximum of 250), however the ADDICT
®
will still reset the time to 0
every 2 hours and will stop if the escape button is pressed.
See page 12 for more details of what is required for PC communications.
The following is an example of the data transmitted by the ADDICT
®
during Sniff to PC:
#ADDICT 1.0 Sniffed packet data
#Live
15.91s 0191 M>A00 Query Ballast
15.96s 0391 M>A01 Query Ballast
16.01s 0591 M>A02 Query Ballast
16.06s 0791 M>A03 Query Ballast
16.07s FF
16.10s 0799 M>A03 Query Dev. Type
16.11s 00
The data transmitted for each sniffed packet is the same as that sent with Send all to PC on the