Transmit to PC
Transmit to PC sends all the device settings that are currently stored in the ADDICT
®
to a PC (or
other device capable of receiving RS-232 serial data) via the PC communications link. Note that
the current version of the Terminal-compatible PC comms is listed correctly in the data set as
“1.0". The following is an example of the data that is sent:
#ADDICT 1.0 Captured settings data
#bus_id addr grps_0-7 grps_8-15 min max fade_time&rate power_on sys_fail scenes*16 xor_checksum
00 01 09 02 01 FE 07 FE FE FE FE FE 01 01 01 01 FE FE FF FF FF FF FF FF 00 01
00 02 0A 02 01 FE 07 FE FE 01 E5 FE FE FE D2 01 01 01 FF FF FF FF FF FF 00 34
00 03 04 00 83 D4 87 FE FE 01 01 01 01 FE FE FE FE C3 FF FF FF FF FF FF 00 19
00 04 00 00 01 FE 07 FE FE C4 DD EC F6 FE FF FF FF FF FF FF FF FF FF FF FF F9
01 01 00 00 01 FE 07 FE FE FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FC
01 02 00 00 01 FE 07 FE FE FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FF FD
01 03 00 00 01 FE 07 FE FE C4 DD EC F6 FE FF FF FF FF FF FF FF FF FF FF FF F8
01 04 00 00 01 FE 07 FE FE C4 DD EC F6 FE FF FF FF FF FF FF FF FF FF FF FF F0
.
All data is sent as 2-digit hexadecimal values, and there is one line for each device. A header line
is also transmitted explaining what each value represents. The final value is an XOR checksum (it
is the XOR sum of all the preceding values) and can used as a simple method for detecting errors
in the data. The last line starts with a “.” indicating the end of the data.
Delete Stored
Delete Stored allows device settings stored in the ADDICT
®
to be deleted (it does not affect the
settings in any actual devices currently connected to the DALI line). Memory slots are deleted by
bus ID (or all slots can be deleted at once). Note: it is not possible to delete the settings for just
a single address, but all addresses for a selected bus ID will be deleted.
When selecting a bus ID, the number of addresses associated with that bus ID (and hence the
number of slots that will be deleted) is displayed:
After a bus ID (or ALL) is selected, confirmation is required before the slots will actually be
deleted.
Selectable values:
Bus ID (0 99, ALL) device settings for addresses associated with the selected bus ID
will be deleted. Press enter to proceed to confirmation
Confirmation (YES, NO) Press enter to confirm deletion of slots, YES to delete, NO to
cancel