User's Manual

INSTALLATION INSTRUCTIONS
0-10V Interface
Wireless 0-10V Dimming/Switching Interface with SmartCast™ Technology
Includes: CIF-10V-CWC-SNSR
LPN00212X0005A3_B
1 of 3
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be
followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. Before installing turn off the power at the circuit breaker.
2. Must be installed in accordance with the national and local building codes and
electrical wiring codes including wiring methods and wiring connections. If you
are not familiar with these codes and requirements, consult a qualied electrician.
3. Indoor use only and suitable for damp locations.
4. Any changes or modications to these devices not explicitly approved by
manufacturer could void your authority to operate this equipment.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
Voltage: 120-277V, 60Hz
Load Type: 120-277VAC 5-2.1A 600W MAX. (Electric Ballast/ General
Purpose (LED))
Install using a junction box that has a 1/2" knockout
UNIT DESCRIPTION
The Cree Wireless 0-10V Interface is used to
wirelessly control LED luminaires that do not
have built in Cree SmartCast ™ Technology. The
Cree Wireless 0-10V Interface provides on, off,
and 0-10V dimming control.
LOAD TYPES
0-10V dimmable loads (IEC60929)
INSTALLATION
NOTE: For ease of installation, Cree
recommends using a Junction Box with a ½"
knockout.
STEP 1:
Disconnect power to circuit by turning circuit
breaker OFF before installation.
STEP 2:
Remove Junction Box cover.
STEP 3:
Remove knockout and firmly install plastic
relay box into Junction Box until it snaps and is
securely attached
STEP 4:
Strip existing Junction Box wires ½".
STEP 5:
Make wiring connection per the Electrical
Connection section.
STEP 6:
Attach Junction Box cover.
STEP 7:
Install sensor into ceiling by drilling a 2" hole
into the ceiling.
1
Blue LED is Inside the Relay Box, Light
will Shine Through at the LED Placement
Shown Below.
Test/Reset
Button Inside
Blue LED
Placement
This End Insert into
Junction Box
Sensor
Interface Box