User's Manual

LPN00212X0005A3_B
2 of 3
STEP 8:
Unscrew the small trim ring near the sensor and place sensor
assembly through the ceiling. See Figure 2.
STEP 9:
Secure the sensor assembly by screwing the small trim ring
removed in Step 8 back onto the sensor assembly. Tighten
the larger trim ring above the ceiling until it is snugged tight
against the ceiling. See Figure 2.
STEP 10:
Switch the circuit breaker ON.
STEP 11:
The blue LED should repeat a two blink sequence. If the blue
LED does not respond with the two-blink sequence, please
follow the RESET instructions to return the 0-10V Interface to
factory defaults.
STEP 12:
Verify the LOAD wiring with the following TEST instructions:
• Press and hold the Test/Reset button for 5 sec then
release. The blue LED should respond with a five-blink
sequence. Once test mode has been entered, LOAD
enters State 1. See Figure 1.
• Press and hold Test/Reset button for 1 sec then
release to transition to the next state. The sequence
repeats after State 3. Please refer to the load table
below for your load type.
• To exit test mode at any time, press and hold the Test/
Reset button for 5 sec then release. The five-blink
sequence ends when test mode is exited.
Dimmable Non-Dimmable
State 1 Off Off
State 2 Max light output (10V) On
State 3 Min light output (1V) On
RESET
STEP 1:
Press and hold Test/Reset button until the LED flashes fast
(approximately 30 seconds).
STEP 2:
Release the Test/Reset button for 1 second (Fast flashing
continues). Press and hold Test/Reset for 1 second until fast
flashing stops. If the blue LED does not respond with the
two-blink sequence, please repeat the RESET procedure.
TROUBLESHOOTING:
Out of the box, if the LOAD does not turn on when power is
applied:
Perform TEST mode to verify proper functionality of the load
type
• If TEST mode fails, check Wiring with power off.
• If wired correctly, check to see if Blue LED is blinking.
• If Blue LED is blinking, then perform a RESET (See
RESET section).
• If Blue LED is on solid or off, call Cree Customer
Service.
• If you have done a RESET, and the LOAD is still off,
call Cree Customer Service.
If LOAD is unresponsive use Cree Configuration Tool to verify
configuration.
2
Sensor
Large Trim Ring
Small Trim Ring
Ceiling