Installation and Operating Manual
User Manual 
040003A010 Rev A      Page 5 of 25   
2  INSTALLATION 
2.1  INSTALLATION INSTRUCTIONS  
The amplifier is designed for installation in a rack that permits access to the rear of the unit for 
connection of RF and monitor/control cables, and DC power cables or AC line cord if the unit 
incorporates the internal AC power supply option. The amplifier must have a minimum of 3 inches 
of open space in front and to the rear of the chassis to allow adequate air flow and ventilation.  If 
installed  in  a  closed  or  multi-unit  rack,  the  operating  ambient  temperature  within  the  rack 
environment  may  be  greater  than  the  room  ambient.    The  equipment  installation  must  be 
compatible  with  the  +60°C  maximum  temperature  rating  of  the  amplifier.    Caution  should  be 
exercised when rack mounting the amplifier to avoid creation of a  hazardous condition due to 
uneven  mechanical  loading.  Avoid  “top-heavy”  or  cantilever  installations  which  may cause the 
equipment rack to become unbalanced. Consideration should be given to the connection of the 
equipment to the AC or DC supply circuit and the effect that overloading of the circuits might have 
on overcurrent protection and supply wiring. Consideration of the appropriate current rating (10A 
for 110-125VAC operation, 20A for +48VDC operation) should be used in addressing this concern. 
Caution  should be  exercised  with  supply  connections  which  are  not  direct  connections  to  the 
branch circuit (e.g. use of power outlet strips). Reliable grounding of rack-mounted equipment 
should always be maintained. 
To install the amplifier, proceed as follows: 
1.  Mount the amplifier in equipment rack and secure in place. 
2.  Connect a properly sized 50 Ohm cable and load (antenna) to the RF OUT connector on 
rear of amplifier. 
3.  Connect the transceiver/exciter output to RF IN connector on rear of amplifier. 
4.  If monitoring of PA is desired, connect alarm cable to MONITOR connector on rear of 
amplifier module. See section 3 for more details about monitor pins. 
5.  Connect a ground cable to the rear panel stud of the amplifier.  A UL Listed ground bonding 
conductor  assembly  is  recommended,  such  as  Harger  p/n  UBC61411/4KIT5, 
UBC61811/4KIT5, or UBC63211/4KIT5. These ground cable interfaces consist of Harger 
p/n 6-6R1 ring tongue lugs crimped to various lengths of Harger p/n 6XLPE133G/YS #6 
AWG ground cable.  
6.  If the unit is the 48 VDC version, measure the DC output voltage of the external power 
supply. DC voltage should be +48 +/- 0.5VDC. Turn off the DC voltage. 
NOTE: 
  Make sure power supply DC is well filtered and well behaved with minimal voltage 
overshoot. 
  Keep  DC  cables  as  short  as  possible  (recommend  no  greater  than  2  feet)  to 
minimize inductive voltage transients. 
  Size DC cables properly to handle the load current to minimize voltage drop during 
times of transmission when current draw is highest. 
WARNING: 
  Turn off external primary DC power before connecting DC power cables. 
  Connect positive primary power wire (+48VDC) to terminal marked +48VDC and 










