User Manual

infiNET™ Thermostat Crestron CHV-TSTATRF
Setup
Identity Code
The MNET ID of the CHV-TSTATRF has been factory set to 01. After an infiNET
device is added to an infiNET network, its MNET ID must be changed to a value that
can be addressed by the control system program (03 to 20). The MNET IDs of
multiple CHV-TSTATRF devices in the same system must be unique. MNET IDs
are changed from a personal computer (PC) via the Crestron Toolbox™. They can
also be changed using the Setup Parameter ability of the CHV-TSTATRF (refer to
“Setup Mode” on page 18). When setting the MNET ID, consider the following:
The MNET ID of each unit must match an ID code specified in the SIMPL
Windows or D3 Pro
/SystemBuilder
program.
Each network device must have a unique MNET ID.
For more details, refer to the Crestron Toolbox help file.
Installation
The location of the thermostat can affect its performance and efficiency. Install the
thermostat away from direct sunlight, drafts, doorways, skylights and windows. Also
make sure the thermostat is conveniently located for programming and do not mount
on an exterior wall.
Thermostats are mounted 60 inches (152.4 cm) above the finished floor (HVAC
industry standard).
The following tools/hardware are required for installation.
Standard single-gang electrical box, mounted horizontally (not supplied)
Phillips screwdriver (not supplied)
Two 1-inch pan head Phillips screws (supplied)
After the wiring has been installed and verified, use the following procedure to
install the CHV-TSTATRF in a standard, single-gang electrical box (refer to
illustration on the following page):
1. Separate thermostat front plate from back plate (you may need to exert force
when removing the faceplate).
2. Turn system power OFF.
3. Connect cabling to the CHV-TSTATRF’s HVAC connectors (refer to
illustrations on pages 9 and 10) and the other end to the control system.
4. Make sure unit is correctly oriented and place it in the electrical box.
CAUTION: Excess wire that is pinched between the CHV-TSTATRF and electrical
box could short out. Make sure that all excess wire is completely inside the electrical
box and not between the box and the CHV-TSTATRF.
5. Attach the CHV-TSTATRF back plate to the electrical box using the supplied
two 1-in. pan head screws.
6. Attach faceplate.
8 infiNET™ Thermostat: CHV-TSTATRF Operations & Installation Guide – DOC. 6490