connection diagram when connecting to a C2N-MNETGW via a control
system.
Indirect Serial Communications Setup Connections
1. Ensure that all devices are connected to the control system and the
control system is connected via serial cable to the PC.
2. Open Crestron Toolbox and click Tools | Manage Address Book
to display a list of available devices. Select a connection to a
control system (if an entry for one exists), or Serial on COM1 as
the connection type. Serial on COM1 is an address book entry for
PC-to-control system communications that is included with
Crestron Toolbox.
3. The PC communication settings specified here should match the
protocol that the control system expects. The usual settings are as
follows:
• Port = COM 1 through COM 8. Select the correct COM port
on the PC.
• Baud rate = Auto-detect.
• Parity = None.
• Number of data bits = 8.
• Number of stop bits = 1.
• Hardware handshaking (RTS/CTS) enabled.
• Software handshaking (XON/XOFF) not enabled.