The following table describes the LED pattern in all modes of operation:
LED Behavior
LED BEHAVIOR DEVICE STATE
LOW In RUN mode, operating
normally.
HIGH Device is in the bootloader. Refer
to “Bootloader” on page 21 for
more information.
Four brief OFF blinks
every eight seconds.
In RUN mode but there is no
communication with a gateway.
1
Four brief HIGH blinks
every eight seconds.
Device failed to acquire with a
gateway.
1
Two brief OFF blinks
every eight seconds.
In RUN mode and communicating
with a gateway but the dimmer is
not addressed in a control system
program.
Blink OFF for ½ second,
LOW for ½ second.
In SET mode.
Blink OFF for one second,
HIGH for one second.
The dimmer is in the Acquire
mode and searching for a
gateway.
Blink OFF for ¼ second,
HIGH for ¼ second.
This touch-settable device is
waiting for user to press a button
to identify it.
2
1. Refer to “Enter ACQUIRE Mode” on page 16.
2. Refer to the Crestron Toolbox help file.
18 • infiNET
™