Crestron Green Light™ DIN-PWS50 ® DIN Rail 50 Watt Cresnet Power Supply Operations & Installation Guide
This document was prepared and written by the Technical Documentation department at: Crestron Electronics, Inc. 15 Volvo Drive Rockleigh, NJ 07647 1-888-CRESTRON All brand names, product names and trademarks are the property of their respective owners. ©2008 Crestron Electronics, Inc.
Crestron DIN-PWS50 DIN Rail 50 Watt Cresnet® Power Supply Contents Crestron Green Light™ DIN Rail 50 Watt Cresnet® Power Supply: DIN-PWS50 1 Introduction ............................................................................................................................... 1 Features and Functions ................................................................................................ 1 Applications............................................................................................
Crestron DIN-PWS50 DIN Rail 50 Watt Cresnet® Power Supply Crestron Green Light™ DIN Rail 50 Watt Cresnet® Power Supply: DIN-PWS50 Introduction The DIN-PWS50 is a 50 Watt Cresnet® Power Supply module designed to snap onto a standard DIN rail for installation in a wall mount enclosure. DIN rail mounting enables modular installation alongside Crestron® DIN Rail lighting and automation control modules and other third party DIN rail mountable devices.
DIN Rail 50 Watt Cresnet® Power Supply Crestron DIN-PWS50 Applications The following diagram shows a DIN-PWS50 in a typical application. DIN-PWS50 in a Typical Application 2 • DIN Rail Power Supply: DIN-PWS50 Operations & Installation Guide – DOC.
Crestron DIN-PWS50 DIN Rail 50 Watt Cresnet® Power Supply Specifications Specifications for the DIN-PWS50 are listed in the following table. DIN-PWS50 Specifications SPECIFICATION Output Power Per Output Port Module Total Ripple/Noise Power Requirements Environmental Temperature Humidity Heat Dissipation Enclosure Dimensions Height Width Depth Weight Available Accessories DIN-BLOCK DIN-HUB Operations & Installation Guide – DOC. 6667A DETAILS 50 Watts (2.
DIN Rail 50 Watt Cresnet® Power Supply Crestron DIN-PWS50 Physical Description This section provides information on the connections, controls and indicators available on your DIN-PWS50. DIN-PWS50 Physical View 4 • DIN Rail Power Supply: DIN-PWS50 Operations & Installation Guide – DOC.
Crestron DIN-PWS50 DIN Rail 50 Watt Cresnet® Power Supply DIN-PWS50 Overall Dimensions 106 mm (4.18 in) 58 mm (2.29 in) 1 2 3 90 mm (3.55 in) 94.2 mm (3.71 in) 4 Operations & Installation Guide – DOC.
DIN Rail 50 Watt Cresnet® Power Supply Crestron DIN-PWS50 Connectors, Controls & Indicators # CONNECTORS*, CONTROLS & INDICATORS DESCRIPTION 1 100-240V~50/60Hz 2 24VDC 3 NET 4 FUSE (2) Sets of (3) captive screw terminals, each set paralleled Line power input, neutral and ground with pass through Maximum wire size: 2.5 mm2 (12 AWG) (1) Green LED indicates 24 Volts DC output at all NET ports; extinguished when fuse is blown (3) 4-pin 3.
Crestron DIN-PWS50 DIN Rail 50 Watt Cresnet® Power Supply Industry Compliance This unit has been manufactured to comply with UL’s Standards for Safety in Canada and the United States. Formal approval is pending. As of the date of manufacture, the DIN-PWS50 has been tested and found to comply with specifications for CE marking and standards per EMC and Radiocommunications Compliance Labelling. NOTE: This device complies with part 15 of the FCC rules.
DIN Rail 50 Watt Cresnet® Power Supply Crestron DIN-PWS50 Setup Network Wiring When wiring the Cresnet® network, consider the following: • Use Crestron Certified Wire. NOTE: Cresnet HP cannot be used. • Use Crestron power supplies for Crestron equipment. • Provide sufficient power to the system. CAUTION: Insufficient power can lead to unpredictable results or damage to the equipment. Please use the Crestron Power Calculator to help calculate how much power is needed for the system (www.crestron.
Crestron DIN-PWS50 DIN Rail 50 Watt Cresnet® Power Supply The DIN-PWS50 is designed for installation on a DIN rail. Refer to the following diagram when installing. Installing the DIN-PWS50 DIN-PWS50 TOP DIN RAIL (NOT SUPPLIED) DIN RAIL RELEASE 1. Place the top of the DIN-PWS50’s rail mount over the top of the DIN rail. 2. Tilt the bottom of the DIN-PWS50 toward the DIN rail until it snaps into place.
DIN Rail 50 Watt Cresnet® Power Supply Crestron DIN-PWS50 Hardware Hookup Connect the Device Make the necessary connections as called out in the illustration that follows this paragraph. Refer to “Network Wiring” on page 8 before attaching the 4-position terminal block connector. Apply power after all connections have been made. WARNING: Prior to connecting the device, turn off power at the circuit breaker. Failure to do so may result in serious injury or damage to the device.
Crestron DIN-PWS50 DIN Rail 50 Watt Cresnet® Power Supply Hardware Connections for the DIN-PWS50 100-240~50/60Hz: FROM AC POWER LINE POWER TO OTHER DEVICES FUSE IS LOCATED UNDER THIS COVER Operations & Installation Guide – DOC.
DIN Rail 50 Watt Cresnet® Power Supply Fuse Replacement Crestron DIN-PWS50 If the DIN-PWS50 does not power up when it is plugged into an AC outlet, the fuse may need to be replaced. The fuse holder is located on the front panel, under the cover in the lower left corner. To replace the fuse: 1. Disconnect power to the DIN-PWS50. 2. Remove the cover from the lower left corner on the front of the DIN-PWS50. 3. Remove the defective fuse from the fuse holder and replace with a new one.
Crestron DIN-PWS50 DIN Rail 50 Watt Cresnet® Power Supply Problem Solving Troubleshooting The following table provides corrective action for possible trouble situations. If further assistance is required, please contact a Crestron customer service representative. DIN-PWS50 Troubleshooting TROUBLE 24VDC LED does not illuminate. POSSIBLE CAUSE(S) CORRECTIVE ACTION DIN-PWS50 is not receiving power. Verify the DIN-PWS50 is connected to an AC power line. Replace fuse with T3.15AH (5 x 20 mm, 250 V, 3.
DIN Rail 50 Watt Cresnet® Power Supply Crestron DIN-PWS50 Check Network Wiring Use the Right Wire Calculate Power In order to ensure optimum performance over the full range of your installation topology, Crestron Certified Wire and only Crestron Certified Wire may be used. Failure to do so may incur additional charges if support is required to identify performance deficiencies because of using improper wire. CAUTION: Use only Crestron power supplies for Crestron equipment.
Crestron DIN-PWS50 DIN Rail 50 Watt Cresnet® Power Supply NOTE: All Crestron certified Cresnet wiring must consist of two twisted pairs. One twisted pair is the +24V conductor and the GND conductor and the other twisted pair is the Y conductor and the Z conductor. Strip and Tin Wire When daisy-chaining Cresnet units, strip the ends of the wires carefully to avoid nicking the conductors. Twist together the ends of the wires that share a pin on the network connector and tin the twisted connection.
DIN Rail 50 Watt Cresnet® Power Supply Crestron DIN-PWS50 Return and Warranty Policies Merchandise Returns / Repair Service 1. No merchandise may be returned for credit, exchange or service without prior authorization from CRESTRON. To obtain warranty service for CRESTRON products, contact an authorized CRESTRON dealer. Only authorized CRESTRON dealers may contact the factory and request an RMA (Return Merchandise Authorization) number.
Crestron DIN-PWS50 DIN Rail 50 Watt Cresnet® Power Supply This page is intentionally left blank. Operations & Installation Guide – DOC.
DIN Rail 50 Watt Cresnet® Power Supply Crestron DIN-PWS50 This page is intentionally left blank. 18 • DIN Rail Power Supply: DIN-PWS50 Operations & Installation Guide – DOC.
Crestron DIN-PWS50 DIN Rail 50 Watt Cresnet® Power Supply This page is intentionally left blank. Operations & Installation Guide – DOC.
Crestron Electronics, Inc. 15 Volvo Drive Rockleigh, NJ 07647 Tel: 888.CRESTRON Fax: 201.767.7576 www.crestron.com Operations & Installation Guide – DOC. 6667A (2020749) 05.08 Specifications subject to change without notice.