Changing the NET ID - ST-LT Workshop Screens (2 of 3)
5. Enter a new NET ID code (in two-digit hexadecimal format) and
depress ENTER. The Workshop responds with the screen shown below
that displays a message stating the “New ID” command has been sent.
Changing the NET ID - ST-LT Workshop Screens (3 of 3)
6. To verify this procedure, depress F4 to perform a network poll.
Confirm that the ST-LT has the new NET ID code.
7. Reconnect other network or modular devices that were disconnected in
step 1.
Dip Switch Settings for GRAFIK Eye Use
An eight-position dip switch is mounted to the ST-LT PC board. The switch
positions (switches 6 and 7 ON) are factory set for typical use of the ST-LT within a
CRESNET II System or SmarTouch STS. However, in certain GRAFIK Eye
systems, the switch positions may need to be altered.
If it is determined that the switch settings must be changed, power down the ST-LT
and complete the following steps.
1. Turn the unit over and place it top-side down on a soft, clean surface.
2. Loosen and remove four screws and washers that secure the top cover
to the ST-LT.
3. Lift, turn the unit over, and place the unit down on its four rubber feet.
Operations Guide - Doc. 5694 Lutron Interface 7