Specifications

CRESTRON
The data field contains the command protocol for the Grafik Eye system. A
description of commands, their operation, and examples are provided in the table
below.
Commands for GRX-AV-RS232 and GRX-AV-RS232/ATC
OPERATION CMD PARAMETERS EXAMPLES
Select Scene
A
[scene][main units]
:A21 select scene 2 on unit 1
:AG78 select scene 16 on units 7 & 8
Scene Lock
SL
[+]or[-][main units]
:SL release all units from scene lock
:SL-6 release only unit 6 from lock
:SL+45 additionall lockout units 4 & 5
Request Scene Status
G NONE :G report scene status of all units on link
Sequence
SQ
[+]or[-][main units]
:SQ release all unitsfrom sequence mode
:SQ-3 release only unit 3 from sequencing
:SQ+68 add units 6 & 8 to sequencing
Zone Lock
ZL
[+]or[-][main units]
:ZL release all units from zone lock
:ZL-1 release only unit 1 from lock
:ZL+36 additionally lockout units 3 & 6
Zone Lower
D
[main unit][zones]
:D5 stop ramping down all zones on unit 5
:D3124 ramp down zones 1,2 & 4 on unit 3
Zone Lower Stop
E NONE :E stop ramping down all zones on all units
Zone Raise
B
[main unit][zones]
:B5 stop ramping up all zones on unit 5
:B3124 ramp up zones 1,2 & 4 on unit 3
Zone Raise Stop
C NONE :C stop ramping up all zones on all units
Set Time*
ST
[hr][min][mth][day]
con. [yr][dayofweek]
:ST 1 35 10 26 95 5 set time and date to 1:35am,
Thursday, October 26, 1995
Report Time*
RT NONE :RT report current time and date of control
response ~:rt
hr min month day yr dayofweek
Select Schedule*
SS
[schedule]
:SS1 start weekday schedule
Report Schedule* RS
NONE
:RS which schedule is currently running
response ~:rs
schedule
Report Sunrise/Sunset* RA
NONE
:RA report sunrise time and sunset time
response ~:ra
rise_hr rise_min set_hr set_min
Super Sequence Start* QS
NONE
:QS start super sequence at first event
Super Sequence Pause* QP
NONE
:QP stop super sequence at current event
Super Sequence Resume*
QC NONE :QC resume super sequence at next event
NOTE: Command operations denoted with an asterisk (*) are for GRX-AV-RS2323/ATC only.
For a more comprehensive description of commands refer to “Appendix: GRAFIK Eye
Commands” on page 18.
Operations Guide - Doc. 5694 Lutron Interface 15