Specifications

CRESTRON
Example of Response:
<CR><LF>~:ss2L0MAR95 1 OK<CR><LF>
Main Unit A1 is in scene 2
Main Unit A2 is sendin
g
a master
lower
Main Unit A3 is OFF
Main Unit A4 is missin
g
Main Unit A5 is in scene 10
Main Unit A6 is sendin
g
a master
raise
Main Unit A7 is in scene 9
Main Unit A8 is in scene 5
(SQ) Sequence
This command determines which GRAFIK Eye Main Units are sequenced (changed
from scene to scene with fade times set by GRAFIK Eye Main Units). Two
sequences can be selected, depending on the setting of dip switch 4. If dip switch 4
is OFF, the GRAFIK Eye Main Units selected by this command sequence through
scenes 1-4. If it is ON, they sequence through scenes 5-16. The command
parameters are the same as for scene lock. Notice that all GRAFIK Eye Main Units
can be taken manually out of sequence mode by switching dip switch 3 from the ON
to the OFF position. Also note that if another GRAFIK Eye accessory is sequencing
a Main Unit, neither this command nor dip switch 3 releases it.
Examples:
:SQ<CR>
Take all GRAFIK Eye Main Units out of sequence
mode .
:SQ2<CR>
Sequence GRAFIK Eye Main Unit 2 and take all
other GRAFIK Eye Main Units out of sequence
mode.
:SQ+68<CR>
Sequence GRAFIK Eye Main Units 6 and 8 (in
addition to the units already selected).
:SQ-3<CR>
Take GRAFIK Eye Main Unit 3 out of sequence
mode, while not affecting the status of other GRAFIK
Eye Main Units.
:SQ-5678 SQ+1<CR>
Take GRAFIK Eye Main Units 5, 6, 7, and 8 out of
sequence mode and sequence GRAFIK Eye Main
Unit 1, but do not change the status of 2, 3, and 4.
(ZL) Zone Lock
When a GRAFIK Eye Main Unit is selected by this command, the intensity of zone
levels preset in its memory cannot be altered. The level of the zone can be changed,
but preset memory is write-protected. The command parameters are the same as for
scene lock and sequence. Notice that all GRAFIK Eye Main Units can be released
manually from zone lock by switching dip switch 1 from the ON to the OFF
position. Also note that if another GRAFIK Eye accessory is holding a Main Unit in
zone lock, neither this command nor dip switch 1 releases it.
Examples:
:ZL<CR>
Release all GRAFIK Eye Main Units from zone lock .
:ZL2<CR>
Zone lock GRAFIK Eye Main Unit 2 and release all
other GRAFIK Eye Main Units from zone lock .
:ZL+68<CR>
Zone lock GRAFIK Eye Main Units 6 and 8 (in
addition to the units already selected).
:ZL-3<CR>
Release GRAFIK Eye Main Unit 3 from zone lock ,
while not affecting the status of other GRAFIK Eye
Main Units.
20 Lutron Interface Operations Guide - Doc. 5694