This command causes the zones of the selected GRAFIK Eye Main Units to
gradually decrease in intensity. The first parameter is the GRAFIK Eye Main Unit
and the second is the zone(s) affected. Any zone numbers not listed are unaffected.
If the command is given for a GRAFIK Eye Main Unit and no zones are listed,
zones that are currently ramping down on that Main Unit stop. Invalid GRAFIK Eye
numbers return an error statement.
Examples:
:D11357<CR>
Ramp down zones 1, 3, 5, and 7 of GRAFIK Eye
Main Unit 1.
:D781 D32<CR>
Ramp down zones 8 and 1 of GRAFIK Eye Main Unit
7 and zone 2 of GRAFIK Eye Main Unit 3.
:D5 D52 D18<CR>
Stop all zones on GRAFIK Eye Main Unit 5 that are
currently ramping down; ramp down zone 2 of
GRAFIK Eye Main Unit 5 and zone 8 of GRAFIK Eye
Main Unit 1.
:D1 D2 D3<CR>
Stop ramping down all zones on GRAFIK Eye Main
Units 1, 2, and 3.
(E) Zone Lower Stop
This command cancels all zone lower commands. It is used as a short cut for sending
the D command with no zones and all GRAFIK Eye Main Units.
Example:
:E<CR>
Stop all zones on all GRAFIK Eye Main Units
that are ramping down.
(B) Zone Raise
This command causes the zone(s) listed on the given GRAFIK Eye Main Unit to
gradually increase in intensity and has the same parameters as zone lower. Zone
numbers not listed are unaffected. If the command is given for a GRAFIK Eye Main
Unit and no zones are listed, any zones on the GRAFIK Eye Main Unit that are
currently ramping up are stopped. Invalid GRAFIK Eye numbers return an error
statement.
Examples:
:B11357<CR>
Ramp up zones 1, 3, 5, and 7 of GRAFIK Eye Main
Unit 1.
:B781 B23<CR>
Ramp up zones 8 and 1 of GRAFIK Eye Main Unit 7
and zone 3 of GRAFIK Eye Main Unit 2.
:B1 B2 B3<CR>
Stop all zones on GRAFIK Eye Main Units 1, 2, and
3 that are currently ramping up.
:B5 B52 B18<CR>
Stop all zones on GRAFIK Eye Main Unit 5 that are
currently ramping up; ramp up zone 2 of GRAFIK
Eye Main Unit 5 and zone 8 of GRAFIK Eye Main
Unit 1.
Zone Raise Stop
This command cancels all zone raise commands. It is used as a short cut for sending
the B command listing no zones and all Main Units.