Crestron ST-CS Current Sensor Module Operations Guide
This document was prepared and written by the Technical Documentation department at: Crestron Electronics, Inc. 15 Volvo Drive Rockleigh, NJ 07647 1-888-CRESTRON All brand names, product names and trademarks are the property of their respective owners. © 2004 Crestron Electronics, Inc.
Crestron ST-CS Current Sensor Module Contents Current Sensor Module: ST-CS 1 Introduction ............................................................................................................................... 1 Features and Functions................................................................................................ 1 Specifications .............................................................................................................. 2 Physical Description...................
Crestron ST-CS Current Sensor Module Current Sensor Module: ST-CS Introduction Features and Functions There are two Crestron® Current Sensor Module configurations available: ST-CS and STI-CS. Configuration is based on the type of power availability. Use the ST-CS with a 120V power supply for 120 VAC devices, and the STI-CS with a 220V power supply for 220 VAC devices. For purposes of this Operations Guide, the term ST-CS is used for either configuration, except where noted.
Current Sensor Module Crestron ST-CS Specifications The following table provides a summary of specifications for the ST-CS module. ST-CS Specifications SPECIFICATION DETAILS Power Requirements 3 Watts (.25A @ 24VDC) - Cresnet or 0.5A @ 12 VDC external power supply (PW-1205 supplied with ST-CS, PWI-1210 supplied with STI-CS) Default Net ID Control System Update Files 18 1, 2, 3 2-Series Control System Version C2-2.000.CUZ or later CEN/CN-TVAV Version 5.10.13V.
Crestron ST-CS Current Sensor Module Physical Description The ST-CS is housed in a black enclosure with labels on the front and rear panels. On the front of the unit there are six LEDs for indicating current status, power, and Cresnet activity. The front panel provides four potentiometers (POTs) for adjusting the current sensing sensitivity. All connections are made on the back of the unit. The proper domestic and international power cords and plugs are used on the ST-CS and STI-CS, respectively.
Current Sensor Module Crestron ST-CS ST-CS Physical Views (120 VAC Version) 1.50 in (3.81 cm) 12VDC .5A NET POWER A NET POWER B POWER IN 90-125VAC 50-60HZ COMBINED OUTPUT 10A MAX CRESTRON ELECTRONICS INC. CRESSKILL N.J. 07626 6.13 in (15.58 cm) 6.32 in (16.06 cm) 6.94 in (17.63 cm) 7.07 in (17.95 cm) CURRENT SENSOR 1.78 in (4.53 cm) 4 • Current Sensor Module: ST-CS PWR NET CRESTRON POWER A FULL PARTIAL POWER B FULL PARTIAL ST-CS Operations Guide - DOC.
Crestron ST-CS Current Sensor Module STI-CS Physical Views (220 VAC Version) 1.50 in (3.81 cm) 12VDC .5A NET POWER A NET POWER B POWER IN 90-220 VAC 50-60HZ COMBINED OUTPUT 6A MAX CRESTRON ELECTRONICS INC. CRESSKILL N.J. 07626 6.13 in (15.58 cm) 6.32 in (16.06 cm) 6.94 in (17.63 cm) 7.07 in (17.95 cm) CURRENT SENSOR 1.70 in (4.32 cm) PWR NET POWER A FULL PARTIAL POWER B FULL PARTIAL STI-CS CRESTRON Ports A number of ports and plugs are provided on the back of the ST-CS.
Current Sensor Module Crestron ST-CS STI-CS Ports and Plugs 12VDC .5A NET NET POWER A POWER B POWER IN 90-220 VAC 50-60HZ COMBINED OUTPUT 6A MAX CRESTRON ELECTRONICS INC. CRESSKILL N.J. 07626 12 VDC .5 A This DC power socket connector is used to supply external power via the supplied 500 mA power pack (1000 mA power pack for STI-CS). The supplied power pack is optional when the ST-CS receives network power.
Crestron ST-CS Current Sensor Module ST-CS Indicators and User Adjustments There are six LED indicators and four POTS located on the front panel of the STCS. Refer to illustration and descriptions below. ST-CS Indicators and Adjustments CURRENT SENSOR PWR NET POWER A FULL PARTIAL CRESTRON POWER B FULL PARTIAL ST-CS PWR (Power) This LED illuminates when 12 volts or 24 volts DC is supplied to the ST-CS.
Current Sensor Module Crestron ST-CS Use the following instructions to set or change the Net ID. 1. Ensure that the device requiring a Net ID change is the only Cresnet unit connected to the control system. 2. Open the Crestron Viewport. 3. From the Viewport menu, select Functions | Set Network ID. The software checks the baud rate and then opens the "Set Network ID" window. 4. In the "Set Network ID" window, select the device requiring a Net ID change from the Current Network Devices text window.
Crestron ST-CS Current Sensor Module NOTE: If the partial power adjustment is not required, it may be placed in any position that does not cause the LEDs to flash. Hookup Connections for ST-CS Cresnet DEVICE REQUIRING CURRENT SENSING NET 24 Y Z G DEVICE REQUIRING CURRENT SENSING NOTE: USE ST-CNB or CNRJ11 (SOLD SEPARATELY) TO CONNECT ST-CS TO CRESNET. 12VDC .5A NET NET POWER A POWER B POWER IN 90-125VAC 50-60HZ COMBINED OUTPUT 10A MAX CRESTRON ELECTRONICS INC. N.J.
Current Sensor Module Crestron ST-CS Threshold Adjustment 1. Attach the ST-CS power plug (labeled POWER IN) to a live AC outlet. 2. Connect the ST-CS to Cresnet; use ST-CNB, CNRJ11 or C2N-HBLOCK (each sold separately). 3. If using the external power pack, attach the supplied power pack to the 12V power connector (labeled 12 VDC .5A). If connecting to Cresnet, 24 VDC is provided by the network. 4. Observe illumination of the PWR LED when power is supplied to the STCS. 5.
Crestron ST-CS Current Sensor Module Earliest Version Software Requirements for the PC NOTE: Crestron recommends that you use the latest software to take advantage of the most recently released features. The latest software is available from the Downloads | Software Updates section of the Crestron website (www.crestron.com). The following are the earliest useable software version requirements for the PC: • SIMPL Windows, any version. Requires SIMPL+ Cross Compiler version 1.1.
Current Sensor Module Crestron ST-CS The System Views lower pane displays the PRO2 system tree (refer to the following graphic). This tree can be expanded to display and configure the communication ports. Expanded PRO2 System Tree C2Net-Device Slot in Configuration Manager To incorporate an ST-CS into the system, drag the ST-CS from the Cresnet Control Modules | Cresnet I/O Control & Other Modules folder of the Device Library and drop it in System Views.
Crestron ST-CS Current Sensor Module ST-CS “Device Settings” Window NOTE: SIMPL Windows automatically changes the Net ID values of a device added to a program if a duplicate device or a device with the same default Net ID already exists in the program. Always ensure that the hardware and software settings of the Net ID match. For Net ID hardware setting details, refer to “Identity Code” on page 7.
Current Sensor Module Crestron ST-CS The device extenders are available with X-Series and 2-Series control systems; they are not available with the ST-CP or CN-Series control systems. To add a device extender, right-click the ST-CS in Program View, point to Insert Device Extender and select the desired device extender. To program a device extender, expand the ST-CS in Program View and drag the device extender to Detail View.
Crestron ST-CS Current Sensor Module from the Downloads | Product Manuals section of the Crestron website (www.crestron.com). Refer to the following figure for a typical connection diagram when uploading files. NOTE: Use a standard DB9 male to female “straight-through” cable. Typical Connection Diagram when Uploading PC Serial Port DB9 Cable Computer Port NET 24 Y Z G Control Processor ST-CNB Cable ST-CS 12VDC .
Current Sensor Module Crestron ST-CS “Port Settings” Window NOTE: The parameters shown in the illustration above are the port settings for a 2Series control system. Consult the Operations Guide for the control system being used for the exact parameter selection. 4. To verify communication, select Diagnostics | Establish Communications (Find Rack). This should display a window that gives the COM port and baud rate.
Crestron ST-CS Current Sensor Module File transfer | Send Program Command 3. The “Send Program” window appears as shown after this step. Click Browse, locate the completed file (.spz for PRO2) and click Open. This displays the program’s header information and enables one or both of the What to Send check boxes. If the program does not contain any SIMPL+ modules, only the SIMPL Program check box is enabled. If it does contain SIMPL+ modules, then the SIMPL+ Program(s) check box will also be enabled.
Current Sensor Module Crestron ST-CS ST-CS Troubleshooting TROUBLE POSSIBLE CAUSE(S) CORRECTIVE ACTION Unexpected response from control system. Network devices are not communicating to the control system. From the Viewport, poll the network (F4) to verify communication. Green PWR LED does not illuminate. ST-CS is not receiving power. Confirm that power pack is securely plugged into outlet and the connector is properly attached to the ST-CS.
Crestron ST-CS Current Sensor Module Return and Warranty Policies Merchandise Returns / Repair Service 1. No merchandise may be returned for credit, exchange, or service without prior authorization from CRESTRON. To obtain warranty service for CRESTRON products, contact the factory and request an RMA (Return Merchandise Authorization) number. Enclose a note specifying the nature of the problem, name and phone number of contact person, RMA number, and return address. 2.
Crestron Electronics, Inc. 15 Volvo Drive Rockleigh, NJ 07647 Tel: 888.CRESTRON Fax: 201.767.7576 www.crestron.com Operations Guide – DOC. 5677A 02.04 Specifications subject to change without notice.