Instruction manual
Hallett 13 & 30 Instruction Manual - Wastewater & Reuse
Released on 1-May-14 – XH115B Page 5 UV Pure Technologies Inc. © 2014
2. INSTALLATION INSTRUCTIONS
Before Beginning Installation
Water Conditions - Pre-treatment Parameters
Note this section is designed to ensure the optimal performance of your Hallett
system. Please review the following pre-treatment parameters prior to
installation.
If any specifications are of concern or unclear please contact your water dealer
or specialist. Note some of the information below is technical in nature and you
may want to contact your water treatment specialist to review the parameters.
IMPORTANT - Should any of the preceding water parameters exceed the
recommended limits, the system will not be serviceable under warranty.
UV Transmittance – The Ultraviolet Transmittance (UVT) impacts the
amount of treatment since UV light is absorbed rather than being
available for disinfection. The minimum UVT level is indicated in the
proposal document prepared by UV Pure. This value will also be
indicated on a label on the front of the unit, on the inside of the unit, and
on the outside of the shipping carton.
Total Suspended Solids (TSS) - The amount of suspended solids
affect treatment by blocking UV light. The maximum TSS level is
indicated in the proposal document prepared by UV Pure.
Biological Oxygen Demand (BOD) - The maximum BOD level is
indicated in the proposal document prepared by UV Pure
Water Capacity:
The water capacity or peak flow, of the Hallett unit will depend on various
parameters such as UVT, TSS, BOD and level of UV dose required. The peak
flow of unit will be indicated in the proposal document prepared by UV Pure. This
value will also be indicated on a label on the front of the unit, on the inside of the
unit, and on the outside of the shipping carton.
Hallett 13
The water treatment range for the Hallett 13 is 0–50 liters per minute (or 0–13.3
U.S. gallons per minute), with a working pressure of 0–690 kPa (or 0–100 psig).
Hallett 30
The water treatment range for the Hallett 30 is 0–113 liters per minute (or 0–30
U.S. gallons per minute), with a working pressure of 0–690 kPa (or 0–100 psig).
The Hallett units used for wastewater or reuse do not include a flow regulating
device that will limit the flow rate. The flow through the units must be
controlled by the customer.
Temperature Requirements:
Where the unit is installed, the ambient temperature should be between 7–38°C
(45–100°F). If the temperature drops below freezing, drain the unit completely to










