Flue Terminal Positions
TERMINAL POSITION MINIMUM DISTANCE
A - Directly below an openable window or other opening e.g. air-brick 300mm
B - Below gutters, soil pipes or drain pipes 75mm
C - Below eaves 200mm
D - Below balconies or car port roof 200mm
E - From vertical drain pipes and soil pipes 75mm
F - From internal or external corners 300mm
G - Above ground, roof or balcony level 300mm
H - From a surface facing a terminal 600mm
I - From a terminal facing a terminal 1200mm
J - From an opening in the car port (e.g. door, window) into dwelling 1200mm
K - Vertically from a terminal on the same wall 1500mm
L -- Horizontally from a terminal on the same wall 300mm
Additional Notes for Car-Ports and other Single Storey ‘add-on’ extensions
1. Any carport or other add-on extension should consist of a roof, or a roof and one wall. If it consists of a
roof and two other walls - the installation shall be treated as suspect and further advice sought.
2. If there is any opening in the carport into the dwelling e.g. door window etc then the terminal must be at
east 1200mm away from that opening. If it is less then the installation must be treated as suspect and
further advice sought. If it is more than 1200mm then D. F. H and I shall also apply where D is the vertical
distance between the lowest point of the roof and top of the terminal.
3. If the roof is plastic then the installation should be treated with great care, as there is no simple way of
protecting the roof.