User manual

Check for satisfactory clearance of combustion products.
Light the appliance and set to maximum input, locate the front and fret in position and leave to warm up for 5
minutes. Check for satisfactory clearance of combustion products by positioning a lighted smoke match in the
centre of the fire opening, 200mm below the canopy and level with the rear edge of the simulated front coal,
see Fig. 21. All the smoke must be drawn into the flue, if spillage occurs, allow a further 10 minutes. The test
should be carried out with all the windows and doors closed, if an extractor fan is situated in the room, this test
should be repeated with the fan running. If there is a connected room with an extractor fan, the test should be
repeated with all the doors to that room opened and the extractor fan running. If there are any other open flued
appliances in the premises, a spillage test should be carried out on these appliances with the fan switched on. If
either the appliance spills or causes another appliance to spill disconnect the gas supply until the fault has been
corrected. Check operation of the flow sense switch (refer to paragraph 7 in the Servicing Section).
Turn off the gas supply to the fire, remove the pressure gauge and then turn the gas supply ON. Fit the fire
front and fret
Demonstrate the lighting and extinguishing procedures to the user.
ADVISE THAT: The appliance is fitted with an Oxy-pilot to prevent the continued operation in the event of
spillage occurring. If the fire shuts off repeatedly the appliance must be turned off and not used until an
expert is consulted.
In severe winds it is possible that these may cause the flow sensing switch (APS) to close and shut down the
fire via the solenoid valve and also prevent the fan from continuing to run. To relight the appliance it will be
necessary to repeat the full lighting sequence.
Any debris or soot is cleared from the appliance. Advise the customer that they should read their Users
Instructions before operating the fire and always follow the advice in the section headed Removal of Debris
or Soot Deposits. The appliance must be serviced regularly by a competent person in accordance with these
instructions and the appliance is checked for spillage in accordance with the method detailed in these
instructions.
That it is advisable to run the fan periodically when the appliance is not in use (summer time) to ensure that
the fan and associated components are exercised and therefore are serviceable when required.
HAND THESE AND THE USERS INSTRUCTIONS TO THE USER.
Page 20