Data Sheet

| Logic Controller | 5 | AUTOMATION.CROUZET.COM | 09/2018
XBP24 XBP24-E XDP24 XDP24-E
Conforming to IEC/EN 61131-2 Type 1
Input type Resistive
Isolation between power supply and inputs None
Isolation between inputs None
Protection against polarity inversions No
Status indicator No On LCD screen
Cable length ≤ 30 m
Outputs
6 A relay output - 2 outputs from O1 to O2
Breaking voltage
250 Va max
Breaking current 6 A
Derating: UL: ≥ 45 °C (113 °F): 4A max
Maximum breaking current in the common IEC @ 25 °C (77 °F): 12 A
IEC @ 60 °C (140 °F) or UL: 10 A
Mechanical life 5 000 000 operations (cycles)
Electrical durability for 50 000 operating
cycles
24 Vc tau = 0 ms: 6 A, tau = 7 ms: 3 A, tau = 15 ms: 1.8 A
Usage category DC-12: 24 V, 6 A
Usage category DC-14: 24 V, 1.8 A
250 Va cos phi = 1: 6 A, cos phi = 0.7: 5 A, cos phi = 0.4: 2.5 A
Usage category AC-12: 250 V, 6 A
Usage category AC-13: 250 V, 5 A
Usage category AC-15: 250 V, 2 A
Minimum switching capacity 100 mA (at minimum voltage of 12V)
Maximum operating rate Off load: 10 Hz
At operating current: 0.1 Hz
Voltage for withstanding shocks In accordance with IEC/EN 60947-1 and IEC/EN 60664-1: 4 kV
Response time Make = 1 cycle time + 8 ms typical
Release = 1 cycle time + 4 ms typical
Built-in protections Against short-circuits: None
Against over voltages and overload: None
Status indicator No On LCD screen
Cable length ≤ 30 m
8 A relay output - 6 outputs from O3 to O8
Breaking voltage
250 Va max
Breaking current 8 A
Derating: CEI ≥ 55 °C (131 °F) or UL: ≥ 45 °C (113 °F): 6A max
Maximum breaking current in the common IEC @ 25 °C (77 °F): C3, C6: 8A; C4, C5: 16 A
IEC @ 60 °C (140 °F) or UL: C3, C6: 8 A; C4, C5: 10 A
Mechanical life 20 000 000 operations (cycles)
Electrical durability for 50 000 operating
cycles
24 Vc tau = 0 ms: 8 A, tau = 7 ms: 3 A, tau = 15 ms: 1.5 A
Usage category DC-12: 24 V, 8 A
Usage category DC-14: 24 V, 1.5 A
250 Va cos phi = 1: 8 A, cos phi = 0.7: 4.75 A, cos phi = 0.4: 3 A
Usage category AC-12: 250 V, 8 A
Usage category AC-13: 250 V, 4.3 A
Usage category AC-15: 250 V, 1.5 A
Minimum switching capacity 100 mA (at minimum voltage of 12V)
Maximum operating rate Off load: 10 Hz
At operating current: 0.1 Hz
Voltage for withstanding shocks In accordance with IEC/EN 60947-1 and IEC/EN 60664-1: 4 kV
Response time Make = 1 cycle time + 10 ms typical
Release = 1 cycle time + 5 ms typical