Datasheet

06/2018
Standard product Product made to order Contact us
Logic Controller
Millenium Evo
Up to 44 I/Os - 16 DI (4 HighSpeed /
8 AI) - 8 DO
Wireless programming & Control
with bluetooth Interface and Crouzet
Virtual Display
Modbus RTU Network (Slave)
Local datalog management
Up to 1000 programing blocks with
intuitive Crouzet Soft to go from
simple to complex applications
XBP24
Base 24 I/O
XBP24-E
Base 24 I/O Ethernet
XDP24
Base 24 I/O
XDP24-E
Base 24 I/O Ethernet
Product selection
LCD display Ethernet network Part number
No No
88 975 001
No Yes
88 975 011
Yes No
88 975 101
Yes Yes
88 975 111
Product selection KIT
Bluetooth Kit (Millenium EVO Ethernet 88 975 111, Bluetooth interface 88 980 112,
Bluetooth receiver 88 980 116)
88 975 911
Bluetooth Kit (Millenium EVO Standalone 88 975 101, Bluetooth interface 88 980 112,
Bluetooth receiver 88 980 116)
88 975 901
XBP24 XBP24-E XDP24 XDP24-E
General characteristics
Part number 88 975 001 88 975 011 88 975 101 88 975 111
Products certication CE, cULus Listed
Conformity with the low voltage directive
(in accordance with 2014/35/EU)
IEC/EN 61131-2 (Open equipment)
Conformity with the EMC directive
(in accordance with 2014/30/EU)
IEC/EN 61000-6-1 (Residential, commercial and light-industrial environments)
IEC/EN 61000-6-2 (Industrial)
IEC/EN 61000-6-3 (Residential, commercial and light-industrial environments)
IEC/EN 61000-6-4 (Industrial)
Power supply earthing None
Overvoltage category 3 in accordance with IEC/EN 60664-1
Pollution Degree : 2 in accordance with IEC/EN 61131-2
Maximum utilization altitude Operation: 2000 m
Transport: 3000 m
Mechanical resistance Immunity to vibrations IEC/EN 60068-2-6, Fc test
Immunity to shock IEC/EN 60068-2-27, Ea test
Resistance to electrostatic discharge Immunity to ESD IEC/EN 61000-4-2, level 3
Resistance to HF interference
(Immunity)
Immunity to radiated electrostatic elds IEC/EN 61000-4-3, level 3
Immunity to fast transients (burst immunity) IEC/EN 61000-4-4, level 3
Immunity to shock waves IEC/EN 61000-4-5
Radio frequency in common mode IEC/EN 61000-4-6, level 3
Conducted and radiated emissions
(in accordance with EN 55022/11 group 1)
Class B
Operation temperature -20 °C (-4 °F) → +60 °C (140 °F) (+40 °C (104 °F) in a non-ventilated enclosure)
UL: maximum surrounding air: +50 °C (122 °F)

Summary of content (7 pages)